Instruction Manual

Page 1
INSTALLATION INSTRUCTIONS FOR LOW AMBIENT KIT
USED ON KG/KC/KH 156-300 PACKAGED ROOFTOP UNITS
507203-02
5/2022
Supersedes 3/2018
2022
LOW AMBIENT KIT
PACKAGED UNITS KITS
AND ACCESSORIES
Shipping and Packing List
10T62
Package 1 of 1 contains:
2- Pressure switches (S11, S84)
1- Wire harness
5- Wire ties
2- Valve depressor tees
6- Insertion wire ties
10T63 & 10T64
Package 1 of 1 contains:
3- Pressure switches (S11, S84, & S85)
1- Wire harness
5- Wire ties
3- Valve depressor tees
6- Insertion wire ties
10T65
Package 1 of 1 contains:
4- Pressure switches (S11, S84, S85, S94)
1- Wire harness
5- Wire ties
4- Valve depressor tees
6- Insertion wire ties
55W72
Package 1 of 1 contains:
3- Pressure switches (S11, S84, & S85)
3- Wire harnesses
5- Wire ties
3- Valve depressor tees
6- Insertion wire ties
55W73
Package 1 of 1 contains:
2- Pressure switches (S11, S84)
2- Wire harnesses
5- Wire ties
3- Valve depressor tees
6- Insertion wire ties
Application
See table 1 for usage.
TABLE 1
Unit Cat. # Assembly
KGA/KCA 180S 10T62
603364-24
KGA/KCA 156H, 210S
KGB/KCB 180S, 210S
10T63
603364-25
KGA/KCA 180H, 210H, 240S, 300S
KGB/KCB 240S
10T64
603364-26
KGA/KCA 240H, 300H
KGB/KCB 300S
10T65
603364-27
KG/KC 180-300* 55W72
LB-107318BD
KH 180, 240 55W73
LB-107318BE
*Units built before 6/24/13.
CAUTION
As with any mechanical equipment, contact with
sharp sheet metal edges can result in personal in
jury. Take care while handling this equipment and
wear gloves and protective clothing.
WARNING
Improper installation, adjustment, alteration, ser
vice or maintenance can cause property damage,
personal injury or loss of life. Installation and ser
vice must be performed by a licensed professional
HVAC installer or equivalent, service agency, or the
gas supplier
The low ambient pressure switches cycle the outdoor fan
while allowing compressor operation in the cooling cycle.
This intermittent fan operation results in a high
evaporating temperature which allows the system to
operate without icing the evaporator coil and losing
capacity. This kit is designed for use in ambient
temperatures no lower than 0°F (-17.8°C) unless
otherwise noted in the Engineering Handbook.
Install a belly-band style crankcase heater on
compressors which don't have one.

Summary of content (12 pages)