User Manual

Parameter setting
6-7
BA2131EN
Fault messages in the error field (Data/Error)
Error class Error
code
Additional
code [hex]
Meaning
0 0 00 No fault
6 3 00 No access permission
6 5 10 Inadmissible job parameter
6 5 11 Invalid subindex
6 5 12 Data too long
6 7 00 The object does not exist
6 8 00 Data types are not identical
8 0 21 Cannot be executed because of local control
8 0 22 Cannot be executed because of unit status
8 0 30 Leave value range
8 0 40 Collision with other values
8 0 20 Service cannot be executed currently
6.3.2 Parameter communication with the controller
Read job
1. Determine the user data of the controller: i. e. determine the location of the DP user data in
the host.
2. Enter the address of the desired parameter in the field Index and subindex (DP output
data).
3. Job/service = Read job and the bit job/handshake“ must be changed (DP output data).
4. Check, whether the bit job/handshake“ is the same for the DP input data and the DP output
data. If the bit job/handshake“ is the same, the response has been received. You should
implement a time monitoring.
5. Check, whether the bit job/status“ is set. If the bit job/status“ is not set, the field
data/error contains the required parameter value. If the bit job/status“ is set, the reading
job is not executed properly and the field data/error“ contains an error information.
Write job
1. Determine the user-data range of the controller, i. e. determine the location of the DP
user-data in the host system.
2. Enter the address of the desired parameter in the field Index and subindex (DP output
data).
3. Enter the parameter value into the field Data/Error.
4. Job/Service = Write job and the bit job/handshake must be changed (DP output data).
5. Check, whether the bit job/handshake“ is the same for the DP input data and the DP output
data. If the bit job/handshake“ is the same, the response has been received. You should
implement a time monitoring.
6. Check, whether the bit job/status“ is set. If the bit job/status“ is not set, the job has not
been executed properly and the field data/error“ contains an error information. Otherwise,
the job has been executed without any faults.
Show/Hide Bookmarks