User Manual

12 Visualisation with »VisiWinNET®«
12.6 OPC tunnel for local visualisation (integrated control system)
119
Lenze · Controller | Parameter setting & programming · Reference Manual · DMS 1.5 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.6.4 Configure OPC tunnel
The OPC tunnel ...
permits »VisiWinNET®« access to the OPC servers of the Controller
"tunnels" all accesses via a special Ethernet port and hence offers the possibility of remote
access by security systems.
The OPCServer.ini configuration file
To be able to access the SoftPLC OPC server, the ...
... configuration name (standard value: PLC1) specified in the OPCServer.ini file must be used.
... respective node address of the device must be entered into the OPCServer.ini file
(value0=<Node address>).
The OPCServer.ini file is on the memory card of the Controller (directory: \USBStorage).
Note!
If the Windows® XP firewall is activated, the port (standard setting: port 56765) needs
to be activated for the OPC tunnel!
Note!
•The OPCServer.ini configuration file contains parameters which must be observed/
edited if the SoftPLC OPC server is to be used for communication.
After edition of the configuration file, the Controller must be restarted for the
changes to take effect.
PLC0=PLC1 <-- Configuration name (standard value: PLC1)
...
[PLC:PLC1]
...
value0=0731 <-- Node address (example: 731)