10 Parameter reference
10.2 Parameter list
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
10.2 Parameter list
This chapter lists all parameters of the operating system in numerically ascending order.
C00002
Note!
The parameter descriptions are based on the software version V03.04.00.
Parameter | Name:
C00002 | Device commands
Data type: UNSIGNED_8
Index: 24573
d
= 5FFD
h
Note:
• Before switching off the supply voltage after carrying out a device command, check whether the device com-
mand has been carried out successfully via the status display under C00003
!
• Before activating the device commands through a master control, please wait for the "ready" message of the
controller.
• The device will reject a write process to C00002/x if the value is >1 and issue an error message.
Drive control (DCTRL)
: Device commands
Selection list
0Off / ready
1On / start
2Work in progress
4 Action cancelled
5No access
6 No access controller inhibit
Subcodes Lenze setting Info
C00002/1 0: Off / ready Load Lenze setting
• All parameters are reset to the Lenze setting.
• Only possible when the controller is inhibited.
C00002/2 0: Off / ready Load parameter set 1
• Load parameter set 1 from the memory module.
C00002/3 0: Off / ready Reserved
C00002/4 0: Off / ready Reserved
C00002/5 0: Off / ready Reserved
C00002/6 0: Off / ready Reserved
C00002/7 0: Off / ready Save parameter set 1
• Saving parameter set 1 in the memory module safe
against mains failure.
C00002/8 0: Off / ready Reserved
C00002/9 0: Off / ready Reserved
C00002/10 0: Off / ready Reserved
C00002/11 0: Off / ready Save all parameter sets
• All parameter sets are saved in the memory module
with mains failure protection.
C00002/12 0: Off / ready Import EPM data
Setting "1: On / start" activates the automatic import
of parameters of the memory module after the error
message "PS04".