10 Parameter reference
10.2 Parameter list | C00095
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00095
C00097
C00098
C00099
C00100
Parameter | Name:
C00095 | Motor magnetising current
Data type: UNSIGNED_16
Index: 24480
d
= 5FA0
h
After the motor to be used has been selected from the motor catalogue, the suitable value can be entered automati-
cally. An automatic detection via the motor parameter identification is possible as well.
Display range (min. value | unit | max. value)
0.00 A 99.00
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00097 | Rated motor torque
Data type: UNSIGNED_32
Index: 24478
d
= 5F9E
h
Display of the rated motor torque
• The value displayed here is calculated from different parameters, e.g. the maximum current set in C00022
.
Display range (min. value | unit | max. value)
0.00 Nm 99.00
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 100
Parameter | Name:
C00098 | Device rated current
Data type: UNSIGNED_16
Index: 24477
d
= 5F9D
h
Display of the rated inverter current which is defined by the integrated power section.
Display range (min. value | unit | max. value)
0.0 A 999.0
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 10
Parameter | Name:
C00099 | Firmware version
Data type: VISIBLE_STRING
Index: 24476
d
= 5F9C
h
Display of the firmware version of the device as string
Read access Write access CINH PLC STOP No transfer COM MOT
Parameter | Name:
C00100 | Firmware version
Data type: UNSIGNED_8
Index: 24475
d
= 5F9B
h
Display of the firmware version of the device, divided into subsections.
Display range (min. value | unit | max. value)
0 99
Subcodes Info
C00100/1 Firmware version - main version
C00100/2 Firmware version - subversion
C00100/3 Firmware version - release
C00100/4 Firmware version - build
Read access Write access CINH PLC STOP No transfer COM MOT Scaling factor: 1