Instruction Manual

Commissioning
Test commissioning
Test commissioning with keypad control
7
88
EDS84ABD302 EN 4.0
7.5.1 Test commissioning with keypad control
Step-by-step commissioning
1. Wiring of power terminals
Make use o f the ”Electrical installation” chapter or the Mounting Instructions to wire the
power terminals according to the requirements of your device.
2. Wiring of control terminals.
Digital inputs at terminal X4 Assignment Information
DI1DI2
DI3
RFR
X4
24EDO1 12I
AR
A1U
GND
DI4
RFR z Controller enable
RFR = High
z Error reset
High Low (edge-controlled)
3. If you can be sure that the frequency inverter is in the default state (Lenze setting),
you can skip this commissioning step. If not, establish the Lenze setting of the
frequency inverter as follows:
-0-
_
`
PASS
2 sec.
0000
_
`
....
`
....
....

`
_
_
_
`
....
C002
c001
01
-1-
8888
_
`
....
84BLMEN001
z Select menu -1- (all parameters)
z Press ”Enter” key
z Set C002 code
z Press ”Enter” key
z Set c001 subcode
z Press ”Enter” key
z Set value ”01”
z Press ”Enter” key