Instruction Manual

Electrical installation
Common control terminals
Important notes
6
211
EDS84ASC552 EN 9.1
Strip cables
According to the selected lock-in position of the shield sheet, strip the control cables. For
this, strip the c able ends and the cable sheath at the shield lug.
The following table shows the stripping length for the control cables depending on the
selected lock-in position of the shield sheet.
X1 X3, X107 X4, X5
84MOTL001_e 84MOTL001_d 84MOTL001_f
ƒ StateLine: stripping dimensions
X1 X3 X4
min. max. min. max.
a
[mm]
a
[mm]
[mm
2
]
[AWG]
a
[mm]
a
[mm]
[mm
2
]
[AWG]
[mm
2
]
[AWG]
110 135
0.2 ... 1.5
24 ... 16
150 175
0.2 ... 1.5
24 ... 16
0.2 ... 1.5
24 ... 16
ƒ HighLine: stripping dimensions
X1 X3 X4, X5 X107
min. max. min. max. min. max.
a
[mm]
a
[mm]
[mm
2
]
[AWG]
a
[mm]
a
[mm]
[mm
2
]
[AWG]
[mm
2
]
[AWG]
a
[mm]
a
[mm]
[mm
2
]
[AWG]
110 135
0.2 ... 1.5
24 ... 16
150 175
0.2 ... 1.5
24 ... 16
0.2 ... 1.5
24 ... 16
115 140
0.2 ... 1.5
24 ... 16
ƒ TopLine: Stripping lengths
X1 X3/X5 X4/X107
min. max. min. max. min. max.
a a a a a a
[mm] [mm] [mm
2
]
[AWG]
[mm] [mm] [mm
2
]
[AWG]
[mm] [mm] [mm
2
]
[AWG]
110 135
0.2 ... 1.5
24 ... 16
150 175
0.2 ... 1.5
24 ... 16
115 140
0.2 ... 1.5
24 ... 16
Note!
Devices including safety engineering have an increased stripping length ”a”:
ƒ by 10 mm when the shield sheet is pulled out to its minimum length
ƒ by 15 mm when the shield sheet is pulled out to its maximum length