Instruction Manual
Commissioning
Quick commissioning
Terminal control
7
248
EDS84ASC552 EN 9.1
Note!
The application ”actuating drive speed” is implemented with the L enze
setting.
MCTRL: Act. speed val.
C00051
0 rpm
After attaching the keypad or
switching on the controller with
keypad attached, the connection
between keypad and controller is
established.
The connection has b een established
when the code C00051 appears in
the display.
Then pr ess the left function key.
SAVE
Par1 8400 StateLineC
User - Menu
Code list
Quick commissioning
SAVE
Par1 Quick commissioning
Terminals
Keypad
EDIT
Load Lenze setting
C00002/1
Starting from ”User menu” scroll down
with button to ”Quick commissioning”
menu
Click right button.
Select ”Keypad” menu.
Click right button.
Code 00002/1:
– Parameterise with left ”Edit”
function key
MCTRL: Act. speed val.
C00051
0 rpm
When the Lenze setting is loaded, the
display goes off for a short time.
When the display goes on again, the
main menu appears.
– The main menu settings can be
defined by the user using codes
C00465 ... C00469.
Press the left function key to go to the
user menu.
4. Enable controller:
– StateLine: Set terminal X4/RFR to HIGH potential (reference: X4/GIO).
– HighLine/TopLine: Set terminal X5/RFR to HIGH potential (reference: X5/GI).
5. Vary the motor speed with the potentiometer or by defining different fixed
setpoints:
DI2 DI1 Motor speed
00Setpoint by potentiometer
0 1 40 % of C00011 (reference speed)
1 0 60 % of C00011 (reference speed)
1 1 80 % of C00011 (reference speed)
ƒ Please observe
– the actual speed value: C00051
–thefrontLEDs( 265)
6. Save the settings with in the keypad.