Instruction Manual

Technical data
General data and operating conditions
4
28
EDS84ASC552 EN 9.1
Supply conditions
AC mains operation
Direct connection
Power systems
TT
Operation permitted w ithout restrictions
TN
With earthed phase EN 61800-5-1 Operation permitted if additional measures are taken:
Overvoltage reduction to overvoltage category II required.
If protection against accidental contact is required for the
control terminals, external measures must be taken.
The measures described for IT systems must be taken.
Operation is not permissible:
With integrated safety system, e.g. E84AVxxxxxxxxBx
IT Observe instructions regarding special measures.
DC-bus operation Direct connection possible for devices with 400 V m ains
connection.
Motors Only use motors suitable for inverter operation. Lenze L-force
motors comply with the requirements.
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Operation at 2/4 kHz, +45 ... +55 °C:
Operation at 8/16 kHz, +40 ... +55 °C:
For operation above +40/+45°C, reduce rated output current
by 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl:
Reduce rated output current by 5 %/1000 m
2000 ... 4000 m amsl: overvoltage category II
Pollution EN 61800-5-1 Pollution Degree 2
Vibration resistance (9.81 m/s
2
=1g)
Transport
IEC/EN 60721-3-2 2M2
EN 61800-2
2...9Hz:amplitude3.5mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5...13.2Hz:amplitud1mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
EN 61800-5-1
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 10 m/s
2
(1 g)