Instruction Manual

Technical data
Rated data
Operation at rated mains voltage 400 V
4
40
EDS84ASC552 EN 9.1
4.2.3 Operation at rated mains voltage 400 V
Basis of the data
Mains Voltage Voltage range Frequency range
U
Lrated
[V] U
Lrated
[V] f[Hz]
3/PE AC 400 320-0%...440+0% 45-0%...65+0%
Mains current at I
aN
Apparent output power Motor power
with external
mains choke
without external
mains choke
U, V, W 4pol.ASM
Type I
LR
[A] I
LR
[A] S
aR
[kVA] P
aR
[kW]
E84AVxxx3714 1.4 1.8 0.8 0.37
E84AVxxx5514 2.2 2.7 1.1 0.55
E84AVxxx7514 2.5 3.6 1.5 0.75
E84AVxxx1124 3.2 4.4 2.0 1.1
E84AVxxx1524 3.9 5.5 2.4 1.5
E84AVxxx2224 5.1 7.3 3.5 2.2
E84AVxxx3024xxS 7.0 9.8 4.6 3.0
E84AVxxx3024xx0 7.0 9.8 4.6 3.0
E84AVxxx4024 8.8 13.1 5.9 4.0
E84AVxxx5524 12.0 18 8.1 5.5
E84AVxxx7524 15.0 20.0 10.3 7.5
E84AVxxx1134 21.0 29.0 14.7 11.0
E84AVxxx1534
1)
29.0 - 20.0 15.0
E84AVxxx1834 36.0 50.4 24.9 18.5
E84AVxxx2234
1)
42.0 - 29.3 22.0
E84AVxxx3034
1)
55.0 - 38.0 30.0
E84AVxxx3734
1)
68.0 - 47.4 37.0
E84AVxxx4534
1)
80.0 - 55.5 45.0
1)
only with external mains choke