EDB8600UE 00387996 Operating Instructions Frequency inverters 8600 series
These Operating Instructions are valid for controllers with the nameplate data: 8601 E.6x.6x 8602 E.6x.6x 8603 E.6x.6x 8604 E.6x.6x 8605 E.6x.6x 8606 E.6x.6x 8607 E.6x.6x 8608 E.6x.6x 8609 E.6x.6x 8610 E.6x.6x 8611 E.6x.6x 8612 E.6x.6x 8613 E.6x.6x 8614 E.6x.6x 8615 E.6x.
How to use these Operating Instructions... To locate information on specific topics, simply refer to the table of contents at the beginning and to the index at the end of the Operating Instructions. These Operating Instructions use a series of different symbols to provide quick reference and to highlight important items. This symbol refers to items of information intended to facilitate operation. Notes which should be observed to avoid possible damage to or destruction of equipment.
General safety and operating instructions for drive converters in conformity with the Low-Voltage Directive 79/23/EEC 1. General In operation, drive converters, depending on their degree of protection, may have live, uninsulated, and possibly also moving or rotating parts, as well as hot surfaces. In case of inadmissible removal of the required covers, or improper use, wrong installation or maloperation, there is the danger of serious personal injury and damage to property.
Contents 3ODQQLQJ )HDWXUHV RI WKH LQYHUWHU VHULHV 7HFKQLFDO GDWD 2.1 2.2 2.3 2.4 2.5 2.5.1 2.5.2 2.5.3 3.1 3.2 3.3 4.1 4.2 4.2.1 4.2.2 4.2.3 4.2.4 5.1 5.1.1 5.2 5.2.1 5.2.2 5.2.3 5.2.4 5.2.5 5.2.6 5.2.7 5.3 5.3.1 5.3.2 5.4 5.
6.1 6.1.1 6.1.3 6.2 6.2.1 6.2.2 6.3 6.3.1 6.4 6.4.1 6.5 6.6 6.6.1 6.6.2 6.
3.7 3.7.1 3.7.2 3.8 3.9 3.10 Control mode V/f characteristic control I0 control Minimum field frequency fdmin Maximum field frequency fdmax Acceleration and deceleration times Tir, Tif &ORVHG ORRS VSHHG FRQWURO 4.1 4.2 4.3 4.4 4.4.1 4.4.2 4.5 4.6 Analog feedback Digital feedback Frequency pilot control Adjustment of the feedback gain Automatic adjustment Manual adjustment Setting of the controller parameters Additional functions 3URJUDPPLQJ RI WKH IUHHO\ DVVLJQDEOH LQSXWV DQG RXWSXWV 5.1 5.2 5.
6.8 6.9 Oscillation damping Load change damping 2YHUORDG SURWHFWLRQV 7.1 7.2 7.2.1 7.2.2 Overload protection of the frequency inverter (I⋅t monitoring) Overload protection of the motor PTC input I²⋅t monitoring 'LVSOD\ IXQFWLRQV 8.1 8.2 8.3 8.4 8.5 Code set Language Display of the actual values Switch-on display Identification 96 96 97 97 97 98 99 99 100 100 100 &RGH WDEOH 6HULDO LQWHUIDFHV 10.1 10.2 10.3 10.3.1 10.3.2 10.3.3 10.3.4 10.3.5 10.3.6 10.3.7 10.3.8 10.3.
Planning 1 Features of the 8600 inverter series Liability • The information given in these Operating Instructions describe the features of the products but do not guarantee them.
2 Technical data 2.1 General data Mains voltage: Output voltage: Output frequency: Chopper frequency: Threshold of the integrated brake chopper: Enclosure: Ambient temperature: Noise immunity: Permissible pollution: Permissible humidity: Influence of installation altitude on the rated current: 8 3 x 480 V AC, 45 to 65 Hz Permissible voltage range: 330 ...
2.2 Dimensions a h g c i b f d g k e Bottom view Type a mm 204 269 360 400 8601-05 8606-07 8608-11 8612-15 2.3 b mm 330 415 500 690 c mm 185 242 300 350 d mm 315 395 480 655 e mm 180 222 249 345 f mm 295 360 440 600 g mm 6.5 6.5 6.5 10.5 h mm 8 8 8 13 i mm 21 30 30 50 k mm 20 26 50 50 Weight kg 7.0 12.5 28.5 60.5 Scope of supply The scope of supply includes: • frequency inverter type 86XX_E • set-value potentiometer • accessory kit incl.
2.4 Application as directed The controllers of the 8600 series are electrical equipment intended for installation in control cabinets of high power plants. The controllers are directed as components • for the control of variable speed drives with three-phase AC motors. • for the installation in control cabinets or control boxes. • for the assembly together with other components to form a drive system. • The controllers correspond to the Low-Voltage EMC directive.
2.5 CE conformity What is the purpose of the EC directives? EC directives are issued by the European Council and are intended for the determination of common technical requirements (harmonization) and certification procedures within the European Community. At the moment, there are 21 EC directives of product ranges. The directives are or will be converted to national standards of the member states.
2.5.1 EC Declaration of Conformity ´95 for the purpose of the EC Low-Voltage Directive (73/23/EEC) amended by: CE mark directive (93/68/EEC) The controllers of the series 8600 were developed, designed, and manufactured in compliance with the above-mentioned EC directive under the sole responsibility of Lenze GmbH & Co KG, Postfach 101352, D-31763 Hameln The compliance with the DIN VDE 0160 / 5.88 with the amendments A1 /4.89 and A2 / 10.88 as well as pr DIN EN 50178 classification VDE 0160 / 11.
2.5.2 EC Declaration of Conformity ´95 for the purpose of the EC directive relating to Electromagnetic Compatibility (89/336/EEC) amended by: 1st amended directive (92/31/EEC) CE mark directive (93/68/EEC) Controller of the 8600 series cannot be driven in stand-alone operation for the purpose of the regulation about electromagnetic compatibility. (EMC regulation of 9/11/92 and 1st amended directive of 30/8/95).The EMC can only be checked when integrating the controller into a drive system.
Considered basic standards for the test of noise immunity: Basic standard IEC 801-2 /91 Test Electrostatic discharge on housing and heat sink IEC 1000-4-3 Electromagnetic fields Frequency range: 26...1000 MHz High frequency field Frequency range: 80...
2.5.
3 Application-specific controller selection 3.1 Applications with extreme overload, peak torque up to 230% of the rated motor torque − For applications where very extreme starting and overload torques are necessary (e.g. presses, drilling machines). M MN I 0 -control 2.3 − The inverter provides 200% of the rated torque for a maximum of 30s. In the event of cyclic overload, the ratio of overload time and cycle time must not exceed 0.2. 1.8 1.
3.2 Applications with high overload, peak torque up to 170% of the rated motor torque − For applications which require a standard overload behaviour of an inverter (e.g. general mechanical engineering, hoists, travelling drives, calenders). − The inverter provides 150% of the rated torque for a maximum of 30s. In the event of cyclic overload, the ratio of overload time and cycle time must not exceed 0.1.
3.3 Application with medium overload, peak torque up to 135% of the rated motor torque − For applications where only small starting and overload torques are necessary (e.g. ventilators, pumps). − The inverter provides 110% of the rated torque for a maximum of 30s. In the event of cyclic overload, the ratio of overload time and cycle time must not exceed 0.1.
4 Installation 4.1 Mechanical installation • • These frequency inverters must only be used as built-in units. Install the inverter vertically with the terminal strips at the bottom. • Allow a free space of 100 mm at the top and bottom. For the units 8612 ... 8615 this free space is also required at both sides. Ensure unimpeded ventilation of cooling air.
4.2 Electrical installation • The drive controllers are equipped with electrostatically endangered components. The service and maintenance personnel must be electrostatically discharged before working at the units. They can discharge by touching the PE fastening screw or another earthed metallic surface in the control cabinet. • All control inputs and outputs of the inverter are mains-isolated. The mains isolation has a basic insulation.
4.2.1 Motor protection The units do not have a full motor protection. For monitoring the motor temperature PTCs or thermal contacts can be used. The connection possibilities are shown on page 28. When using group drives, a motor protection relay is required for each motor. When using motors which do not have a suitable insulation for inverter operation: - Connect motor filters for protection (see page 43). Please contact your motor manufacturer.
4.2.3 CE-typical drive system Components of the CE-typical drive sytem System components Controller Specification Unit types 8600 For type designation see inner cover page RFI filter For data and data assignment see chapter 6.6, section: Planning of the Operating Instructions. Mains choke For data and data assignment see chapter 6.2, section: Planning of the Operating Instructions.
Installation • Connect the inverter, mains filter, and mains choke to the grounded mounting plate. Zinc-coated mounting plates allow a permanent contact. If the mounting plates are painted, the paint must be removed in every case. • When using several mounting plates they must be connected with as large surface as possible (e.g. using copper bands). • Connect the screen of the motor cable to the screen connection of the inverter and to the mounting plate of a surface as large as possible.
Part of the CE-typical drive system on mounting plate L1 L2 L3 Connection mains fuse Paint-free bare metal contact surfaces Controller Mains choke Paint-free bare metal contact surfaces LINE Mains filter LOAD PE L1 L2 L3 U V W Paint-free connection of a large surface to the mounting plate Conductive connection between mounting plate and PE required PE PE bar PE connection Cables betweem mains filter and controller longer than 0.
This page is empty ! 25
5 Wiring 5.
5.1.1 Tightening torques of the power terminals Type Tightening torque 5.2 8601...8605 0.6...0.8 Nm (5.3...7.1 lbfin) 8606, 8607 8608...8611 1.2...1.5 Nm 1.5...1.8 Nm (10.6...13.3 lbfin) (13.3...16 lbfin) 8612, 8613 6...8 Nm (53...70 lbfin) 8614, 8615 15...20 Nm (133...
168k 5.2.1 Analog inputs and outputs 1 2 + 47k 168k X1 168k 250R 100k 100k S1/4 +10V -10V 7mA 7mA GND GND 3 4 + 7 8 9 10 X4 60 62 63 + Master voltage/ Master current R > 2.2k (unipolar set-value) (bipolar set-value) R > 4.7k Set-value 2 Feedback Set-value 1 Monitor outputs 5.2.
5.2.3 Description of the analog inputs and outputs Analog inputs Terminal Switch setting 1, 2 3, 4 ON S1 1 2 3 Use (factory setting) Level/Resolution Set-value 2 -10V...+10V 12bit + sign -10V...+10V 12bit + sign Actual value OFF Parameter setting see page 66 73 and 66 Actual value -30V...+30V 12bit + sign 73 and 66 Actual value -60V...+60V 12bit + sign 73 and 66 Actual value -90V...+90V 12bit + sign 73 and 66 Actual value -120V...
5.2.5 Digital inputs and outputs The functions for the digital inputs and outputs shown below are factory-set. To switch the signal cables, only use relays with lowcurrent contacts. Relays with gold-plated contacts have proven for this. All digital inputs and outputs are PLC compatible and are - when operated with an external voltage supply (24 V) - isolated from the rest of the control stage. To connect the voltage supply, use terminals 39 and 59.
Internal voltage supply (15V) Inputs: Input voltage: 0 to 30 V LOW signal: 0 to 5 V HIGH signal: 13 to 30 V for 15 V 5 mA per input Input current: Outputs: Maximum voltage supply: Maximum output current: 30 V 50 mA per output external resistor at least 300 Ω for 5 V, e.g. relay part no. 326 850) 50mA 50mA 50mA 50mA 50mA 50mA 10R 50mA 3k 3k 3k 3k 3k 3k 3k 3k 3k 3k +15V 100mA 22k GND X2 S2 X3 20 21 22 28 E1 E2 E3 E4 E5 E6 2.7k 10k GND ext.
5.2.
5.2.7 Frequency output 6⋅ fd If you want to display, for example, the output frequency or the speed of the drive via a digital display device, you can use the frequency output "6 times field frequency". As factory setting, this function is assigned to terminal A4. This output is, like the other digital outputs, isolated and can be supplied via terminals 39 and 59. digital output 10k 2k7 S2 X3 39 X4 A4 59 + n digital tacho ( Lenze type 322 ) - supply 15...
5.3 Operation with DC bus supply 5.3.1 Connection of several drives for energy-sharing Drives which are supplied by a three-phase voltage can also be linked via the terminals +UG and -UG for energy-sharing. This type of connection requires all controllers to be supplied simultaneously with the same mains voltage, with each controller being connected to the recommended mains choke. 8600 8600 L1/2/3 +UG-UG 8600 L1/2/3 +UG-UG * L1/2/3 +UG-UG * * further contr.
5.4 Screenings Cable screenings increase the noise immunity of the drive system and reduce the interfering radiation. The power and control terminals of the inverters are noise immune without screened cables up to severity class 4 to IEC 801-4. Burst of 4kV on the power terminals and 2kV on the control terminals are permissible. Screenings are only required when you want to operate the inverter in environments, where severity class 4 is not sufficient.
6 Accessories Accessories are not included in the scope of supply. 6.1 Brake resistors In the generator mode, e.g. when decelerating the drive, the machine returns energy to the DC bus of the controller. If large inertias are braked and/or short deceleration times are set, the DC bus voltage may exceed its maximum permissible value. In the case of overvoltage in the DC bus, the controller sets pulse inhibit and indicates "overvoltage ".
6.1.1 Selection of the brake resistor • The following combinations ensure - a maximum braking time of 15 seconds - a maximum relative duty time of 10%. • The set continuous power of the inverter is the reference for the combination. Operation at rated power (factory setting) Inverter type Resistor/Ω Power/kW Order number 8601 370 0.15 ERBM370R150W 8602 370 0.15 ERBM370R150W 8603 240 0.2 ERBM240R200W 8604 180 0.3 ERBD180R300W 8605 180 0.
• If the above conditions do not apply, you can determine the suitable brake resistor as follows: 1. Determine the resistance: Resistance [Ω] ≤ [ ] 765 2 V 2 required peak brake power [W ] Depending on the unit the resistances must not fall below the following values: Inverter type minimum resistance 8601 180Ω 8602 180Ω 8603 180Ω 8604 180Ω 8605 180Ω 8606 100Ω 8607 100Ω Inverter type minimum resistance 8608 33Ω 8609 33Ω 8610 33Ω 8611 33Ω 8612 15Ω 8613 15Ω 8614 15Ω 8615 15Ω 2.
6.1.3 Technical data of brake resistors All listed brake resistors are equipped with an integrated temperature monitoring. The brake contact which is switched in the event of overtemperature is designed for: • max. 250 V AC • max. 0.
Moulded module resistors on heat sink e c k d b g a Resistor Resistance Order number Ω 370 240 ERBM370R150W ERBM240R200W Brake resistor Resistance Order number Ω 370 ERBM370R150W 240 ERBM240R200W 6.2 a mm b mm c mm 80 80 240 340 70 70 Power kW 0.15 0.2 Dimensions d e mm mm 225 325 95 70 Resistor values Peak brake power kW 1.4 2.2 g mm 5 5 k mm 7.5 7.
6.2.1 Selection of the mains choke • The set permanent power of the inverter is the reference for the combination. Operation at rated power (factory setting) Inverter type Rat. mains curr./A Inductivity/mH Current/A Order number 8601 3.0 3 x 2.5 7.0 ELN3-0250H007 8602 3.9 3 x 2.5 7.0 ELN3-0250H007 8603 5.5 3 x 2.5 7.0 ELN3-0250H007 8604 7.0 3 x 1.6 12.0 ELN3-0160H012 8605 8.8 3 x 1.6 12.0 ELN3-0160H012 Inverter type Rat. mains curr./A Inductivity/mH Current/A Order number 8606 12.0 3 x 1.2 17.
6.2.2 Technical data of mains chokes k e f n m c a 42 d b Mains choke Order number a b mm mm c mm d mm e mm f mm k mm m mm n mm Weight kg 7A / 2.5mH 12A / 1.6mH 17A / 1.2mH 25A / 1.2mH 35A / 0.88mH 45A / 0.75mH 55A / 0.88mH 85A / 0.38mH 105A / 0.27mH 130A / 0.
6.3 Motor filter Advantages of using a motor filter: • The motor filter reduces capacitive currents caused by parasitic cable capacitances. • The slope of the motor voltage (dv/dt) is limited to 500 V/µs. Motor filters are always required for: • unscreened cables longer than 100m. • screened cables longer than 50m. • when using motors which do not have suitable insulation for inverter operation. (Observe data of the motor manufacturer.
6.3.1 Technical data of motor filter c d e a b Design A c f e d b a Design B Filter type Design Rated current A 4.0 A A 10.0 A A 25.0 A B 55.0 A Order number ELM3-030H004 ELM3-014H010 ELM3-007H025 ELM3-004H055 a mm 210 280 280 500 b mm 75 92 130 235 c mm 160 175 256 185 d mm 197 267 267 400 e mm 50 65 100 220 f mm − − − 40 Weight kg 3.5 6.5 15 40 With motor currents > 55 A please use motor filters which are connected in parallel.
6.4 Motor voltage filter Advantages of using a motor supply filter: • Sinusoidal output voltages to supply electronic devices. Please note: • Install the motor supply filter as close as possible to the inverter. • Select the control mode "V/f characteristic control" (C006=-0-). The "magnetizing current control" form of control is not permissible. • The chopping frequency must be set to 8 kHz (C018 = -4-).
6.4.1 Technical data of motor supply filters c d e a b Design A c g e d b a Design B Filter type Design Rated current A 4.0 A A 5.5 A A 7.0 A A 9.5 A A 13.0 A A 16.5 A B 24.0 A Order number EZS3-004A001 EZS3-006A001 EZS3-007A002 EZS3-010A002 EZS3-013A001 EZS3-017A001 EZS3-024A001 a mm 210 280 280 280 280 280 325 b mm 75 92 92 130 130 130 200 c mm 160 175 175 256 256 256 170 d mm 200 270 270 267 267 267 260 e mm 50 65 65 100 100 100 185 g mm − − − − − − 40.0 Weight kg 4.0 8.0 8.0 16.
6.5 Cable protection Cable protecting fuses for recommended cross-sections: Inverter type Rated fuse current Cable cross-section 8601 - 03 16 A 2.
6.6 RFI filters Advantage of using a RFI filter: • Reduction of high-frequent radio interference. Please note: • Because of the generation of leakage currents, the RFI filters must be connected to earth. The RFI filter must always be connected to earth at first even if you only want to test the system. Otherwise, the system is not protected against shock. • The filters listed in the following can be connected to the 400 V mains.
6.6.2 Technical data of RFI filters c b c b g g fe e d f d a a Design A Design B Filter type Design Rt. current A 8.0A A 16.0A A 25.0A A 36.0A A 50.0A B 80.0A B 110.0A B 180.0A 6.
7 Accessories for networking We will be pleased to send you further information detailing these accessories on request. 7.
7.3 Connecting elements for optical fibre cables−LECOM-LI Lenze offer a series of specially designed connection accessories for the inverters, in order to use the fibre optic communication bus. The accessories included adapters with optical transmitter and receiver, a distributor and power pack. Due to the optical fibre cables, data transmission with a very high immunity to interferences is possible. 7.
8 Initial switch-on Which settings are necessary for the drive to operate? After mains connection the inverter is ready to operate after approx. 0.5 seconds. The frequency inverters are factory-set such that a four-pole standard motor with 400V rated voltage and 50Hz according to the combinations in section 3.1 can be operated without further settings. In case of motor ratings according to section 3.2 or 3.3, page 17ff, it is necessary to increase the permanent output power accordingly.
Parameter setting 1 Keypad Plain text display Display of status: LENZE 8600 UMRICHTER RDY Ready for operation (LED green) I max Imax-limit reached (LED red) IMP Pulse inhibit (LED yellow), released by: PRG SH − Controller inhibit − Fault indication (TRIP) − Undervoltage/overvoltage STP Operating keys 1.
2 Basic control operations Programming of the frequency inverter enables the drive to be adapted to your application. The possible settings are arranged in codes, which are numbered in ascending order and start with the letter "C". Each code provides one parameter which can be selected according to the application. Parameters can be absolute or relative values of a physical unit (e.g. 50Hz or 50% related to fdmax) or numerical codes giving certain status information (e.g.
The arrow position marks whether you are in the code or in the parameter level. → C O u 0 t 5 p 0 u t f r 0 e . q 0 u e H n z c . e 0 n H y z c y Press, until C011 is displayed → m C a 0 x 1 . 1 f r e 5 q 0 u Press PRG to change to the parameter level m C a 0 x 1 . 1 f → r e 5 q 0 u . e 0 n H y z c . e 0 n H y z c Press, until 60 Hz is displayed m C a 0 x 1 . 1 f → r e 6 q 0 u The maximum field frequency of 60Hz is now set and is accepted immediately.
2.1.1 Parameter setting by two codes Some parameters are set by two codes. A preselection code is used to select the parameter which is to be changed. The parameter is then changed by another code. For example, to set the JOG frequency JOG3, first set the preselection code C038 to -3- and then set the desired frequency for JOG3 via code C039. 2.2 Save parameters After the acceptance, new parameters are saved in the RAM until the inverter is connected to mains voltage.
3 Basic settings 3.1 Operating mode The inverters of the 8600 series offer different interfaces. From these you can select each one for control and programming. Controller interfaces for control and programming: Terminals The terminals are exclusively used to control the inverter. Keypad The five keys and the plain text display can be used mainly for programming. A control via the keypad is also possible.
3.1.1 Controller enable Depending on the selected operating mode (C001) different procedures are necessary to enable the controller. Terminal control, i.e. C001 = -0-, -2-, -4- • Apply a voltage between 13 and 30V across terminal 28. • If you have pressed the STP key, enable the controller with SH + STP in addition. In case of terminal control, C040 serves as a display: • C040 = -0- means controller is inhibited. • C040 = -1- means controller is enabled. Control via keypad, i.e.
In case of control via the keypad or the LECOM interface, quick stop can also be (de-)activated via C042. Code C042 Parameter -0-1- Meaning Deactivate quick stop Activate quick stop Acceptance SH + PRG If you want to deactivate quick stop: • Apply a voltage between 13 and 30V across terminals 21 or 22 (CCW rotation). • If you have set C042 to -1- via the keypad or one of the LECOM interfaces, deactivate quick stop in addition by setting C042 to -0-.
3.2 Configuration Using code C005 you can determine the internal control structure and the use of the set-value and feedback inputs.
3.2.1 Example of how to select a configuration The direction of rotation of the motor in a system is to be determined by the sign of the analog set-value (0...+10V for CW rotating field, 0...10V for CCW rotating field). A closed-loop speed control is to be used, for which a DC tacho serves as feedback. A set-value 2 is not used.
3.3 Signal flow chart X1 1 + A 8 D 7 1 -1 + -1 1 Analog set value unipolar ( f dmin ...f dmax ) 1 1 0 S1/4 C025 Master current C027 Gain 0...20mA / 4...20mA C025 C026 Offset 250R C034 f dmin 1 X5 . D .. .
Ramp generator for quick stop Ctrl. enable, -> Reset DC braking 0 Ramp generator output = ramp generator input 1 t Start value A1 A2 A3 Free digital outputs C105 C241 Window ramp generator output = ramp generator input Deceleration time Keypad, LECOM Keypad, LECOM -1-0-, -1-, -2- Ctrl.
3.4 Features of set-value 1 An analog entry of set-value 1 is possible via input X1/terminal 8, otherwise it is entered via the keypad or the LECOM interfaces. This depends on the selected operating mode (C001). The configuration determines whether the input is unipolar, bipolar, or independently of the operating mode, a digital frequency input. With terminal control you can read set-value 1 under code C046.
3.4.2 Digital frequency input With the corresponding configuration (C005) you can use the 9-pole Sub-D socket X5 or X8 as digital frequency input, where two complementary signals shifted by 90° are provided. If you use an HTL-encoder, it is sufficient to provide only the signals A and B. The inputs A\ and B\ must then be bridged using +Vcc (pin 4). The maximum input frequency is 300 kHz for TTL encoders and 100 kHz for HTL encoders.
3.5 Features of set-value 2 Set-value 2 can only be provided via the differential input X1/terminals 1,2, independently of the selected operating mode (C001). Its value can only be displayed in per cent under code C049. Set-value 2 is processed first by a special ramp generator, before it is added to set-value 1.The ramp times of the ramp generator are set separately via C220 and C221. Code C220 C221 Parameter 5.0s 0.0 to 990s 5.0s 0.
Gain Set the signal gain after the offset adjustment. First apply that signal to which you want to adjust the internal display (see offset). Then select under C025 the corresponding analog input. Adjust the signal gain such that the desired set-value is obtained. For the adjustment of the feedback input see pages 73 and 75. Code C025 Parameter -1-2-4-1000...+1000 mV (factory setting) 1.000 -2.500...+2.500 C026 C027 3.
3.7.1 V/f characteristic control You have to change from I0 control (factory setting) to V/f characteristic control if you want to supply several drives with different loads or rated power from one inverter. Also for pump and blower drives to be operated with a square characteristic, a V/f characteristic control is required. V/f characteristic With V/f characteristic control the output voltage is controlled according to the characteristic set via C014 and C016.
Voltage boost Vmin In the low speed range, the obtained torque is determined largely by the set voltage boost. If you set Vmin (C016), make sure that the motor cannot be destroyed by overheat. Experience tells that self-ventilated standard asynchronous machines of insulation class B can be operated in a frequency range up to 25Hz only for a short time with rated current. Therefore proceed as follows: • The motor should be operated in idle running. • Provide a set-value of 4 to 5 Hz.
3.7.2 I0 control "I0 control" is especially suited for machines with a large breakaway torque. Compared to the V/f characteristic control it provides considerably larger torques up to the motor rated point. The advantages of I0 control can be used especially for single drives. It is also possible for group drives, provided that the motors are of the same type and have the same load, e.g. two identical drives, which drive a common shaft from two sides.
3.8 Minimum field frequency fdmin You can use code C010 to program a minimum output frequency. This changes the influence of the analog set-value to set-value 1 in the factory-set configuration C005 = -0- (not for other configurations). set-value 1 fdmax fdmin 0 100% analog set-value X1/term. 8 For set-value inputs via keypad or LECOM interfaces, the fdmin setting is not effective. Code C010 3.9 Parameter 0.0Hz 0.0...
3.10 Acceleration and deceleration times Tir, Tif The ramp generators (main set-value, set-value 2) are programmed using the acceleration and deceleration times. Under C012 and C013, the ramp generator for the main set-value (Setvalue 1/JOG frequency) receives its standard setting. The acceleration and deceleration times refer to a change of the field frequency from 0 to the maximum field frequency set under C011.
4 Closed-loop speed control For a number of applications, the accuracy which can be obtained with open-loop speed control is often not sufficient. To avoid a speed reduction which occurs when an asynchronous motor is loaded, you can select a configuration with a PI controller. The appropriate configuration depends on the way of set-value input and the actual value input you want to use.
4.3 Frequency pilot control For applications where the feedback signal is directly proportional to the speed of the drive (actual speed) it is advantageous to pilotcontrol the output frequency with the set-value or feedback. The influence of the PI controller can be limited such that only the maximum machine slip to be expected is controlled.
Closed-loop control without pilot control, closed-loop control of an application datum The PI controller is normally used for the speed control of the connected motor. The large setting ranges of the control parameters also allow the control of an application datum if this depends on the drive speed. For this it may be necessary to switch off the frequency pilot control and to set the PI controller to 100% influence.
4.4.2 Manual adjustment If, for technical reasons, the above described automatic adjustment in idle running is not possible or too inaccurate, you can measure the motor speed by hand and calculate the required feedback gain. Proceed as follows: • Activate the closed-loop speed control (C005) with pilot control of the output frequency by the controller reference (C238 = -1-). • If possible, enter 100% set-value. If the set-value is smaller, the obtainable adjustment result is normally less precise.
4.6 Additional functions For special applications, you can use a variety of additional functions: ,QSXW LQWHJUDO DFWLRQ FRPSRQHQW Using this function, the integral action component (I-component) of the PI controller can be reset to zero. You can activate this additional function via one of the freely assignable digital inputs. Fur further information about programming of the freely assignable inputs see page 78. This function is e.g.
5 Programming of the freely assignable inputs and outputs Most of the inputs and outputs of the frequency inverter are freely assignable via their own codes, i.e. they can be especially assigned to the required signals. Furthermore, these signals can be adjusted in the best possible way by setting facilities. In factory setting, these inputs are already assigned to certain functions. 5.
Except for the functions "Enable JOG frequencies", "Enable additional acceleration and decleration times" and "Select parameter set", every function can only be assigned to one terminal. If you want to re-assign an input, the previous programming is lost. A function can only be assigned to one input. A double assignment is not possible. 5.2 Functions of the freely assignable digital inputs 5.2.1 Set TRIP The inverter receives a TRIP message via the assigned input.
Extended operation of the DC injection braking may cause the motor to overheat! Code C036 C107 Parameter 0.0% 0.0...40% 999s 0.0...999s Meaning Voltage for DC injection braking Acceptance ON-LINE Holding time for DC injection braking 999s = Holding time not limited ON-LINE With terminal control C048 serves as display whether the DC injection braking is active or not. With control via the keypad or the LECOM interfaces the DC injection braking is (de-)activated via C048.
Assignment of the digital inputs The number of required inputs for the function "Enable JOG frequency" depends on the amount of the required JOG frequencies. JOG frequencies Number of required JOG frequencies 1 2...3 4...7 8...15 Number of required inputs at least 1 at least 2 at least 3 4 A maximum of four inputs can be assigned to this function. For the assignment of the inputs see the notes on page 78.
5.2.5 Additional acceleration and deceleration times For the ramp generator of the main set-value (set-value 1/JOG frequency) you can call additonal acceleration and deceleration times from the memory, e.g. to change the acceleration speed of the drive as from a certain speed. Programming of additional acceleration and deceleration times The ramp times are set in two steps, under C100, one pair of acceleration and deceleration times is selected.
Enabling the additional acceleration and deceleration times With terminal control activate the assigned digital inputs according to the table below. The input with the smallest number is the first input, the input with the next highest number is the second input, etc. (e.g. E7 = first input, E8 = second input).
5.2.6 Ramp generator stop While the drive is accelerated via the ramp generator of the main set-value, you can hold the ramp generator using the assigned digital input, e.g. to wait for certain actions before accelerating. With terminal control you can read under C131 whether the ramp generator is stopped or not. With control via the keypad or the LECOM interfaces the ramp generator (main set-value) is stopped and enabled again under C131.
5.2.10. Select parameter set, Load parameter set You can store up to four different parameter sets, for example when you want to process different material with one machine or if you want to run different motors with one inverter. Programming of parameter sets To program several parameter sets, the following steps are required: • Enter all settings for one application. • Select code C003 and save your parameter set for example under -1- (parameter set 1). • Enter all settings for another application (e.g.
With control and programming via keypad or LECOM interfaces you can start the loading of a parameter set under C002. Under C002 you can also load the factory setting. Code C002 5.
Every function can only be assigned to one output, including the relay output. If you want to re-assign an output, the previous programming is lost. A function which is already assigned to an output, can only be assigned to another terminal or the relay output, if the previously used output has been assigned to another function. 5.4 Functions of the freely assignable digital outputs 5.4.
5.4.4 Fault indication TRIP A fault is indicated via the permanently assigned digital output terminal 41 and - in factory setting - via the relay output. If you need the output terminal 41 with reverse polarity, you have to use a freely assignable output and set the polarity as required. Before, the relay output must be assigned to another function. 5.4.5 Ready, RDY The status "ready" is indicated approximately 0.
5.4.9 Flying restart circuit active If you have activated the flying restart circuit, the assigned output indicates when the flying restart circuit is active. For further information about the flying restart circuit see page 95. 5.4.10 Process control active, process step active If you use the process control, the assigned outputs indicate when the process control or individual steps are active. For further information about the process control see page 94. 5.
5.6 Digital frequency output X9 (Option) The connection of drives via digital frequency allows a simple and precise control of multi-motor systems. The digital frequency output X9 can be used here as digital frequency encoder, e.g. for parallel or slave drives.
6 Additional open-loop and closed-loop control functions 6.1 Chopping frequency The inverters of the 8600 series offer the feature to adapt the chopping frequency of the inverter to the noise and smooth running requirements of the motor. By increasing the chopping frequency you can generally reduce the motor noises which are generated by the pulsating output voltage. By reducing the chopping frequency the smooth running in the low frequency range is often improved.
6.1.1 Automatic chopping frequency reduction If you want to operate the frequency inverter with 4 kHz (C143 = -2- to -6-) or a higher chopping frequency, but also require an improved smooth running with low speeds, you can activate an automatic chopping frequency reduction, restricted to this range. For this, enter the output frequency under C143, below which the chopping frequency is to be reduced automatically to 2 kHz.
6.4 S-shaped ramp generator characteristic For the ramp generator of the main set-value you can select two different characteristics under C134: • linear characteristic for all constant accelerations • S-shaped characteristic for all jerk-free accelerations. Code C134 6.
6.6 Process control By programming a process control you can enter fixed speed profiles which are processed automatically. The process control can consist of a maximum of eight process steps. Each step consists of a set-value (C211), an acceleration or a deceleration time (C212) and the duration of the step (C213). The number of the step to be processed next is entered via C214. Program the process control as follows: • Under C210, select the process step which you want to program.
Activating the process control With terminal control you can activate the process control via one of the freely assignable digital inputs. With control via keypad or the LECOM interfaces the process control is (de-)activated under C044. Code C044* Parameter -0-1- Meaning Finish process control Process control active Acceptance SH + PRG * extended code set The process control always starts with step 1.
Rated motor power By entering the rated motor power (C081), the flying restart circuit is adapted to the motor. If the rated motor power is programmed correctly, the obtainable flying restart accuracy shows the best results. Code C081* Parameter -4-5-6-7-8-9-10-11-12-13-14-15-16-17-18-19-20-21-22-23-24- Meaning 0.25kW 0.37kW 0.55kW 0.75kW 1.1kW 1.50kW 2.20kW 3.0kW 4.0kW 5.5kW 7.5kW 11.0kW 15.0kW 18.5kW 22.0kW 30.0kW 37.0kW 45.0kW 55.0kW 75.0kW 90.0kW Acceptance SH + PRG * extended code set 6.
7 Overload protections 7.1 Overload protection of the frequency inverter (I⋅t monitoring) The frequency inverters have an output current monitoring to protect them against overload. You can adapt this protection to the maximum ambient temperature to be expected. The lower the max. ambient temperature, the higher the limit of the permissible continuous output current. The permissible continuous output power rises the same way.
7.2.2 I²⋅t monitoring The motor temperature can be calculated and monitored by the inverter. Set the motor monitoring as follows: • Enter the motor frame size under code C086 together with the kind of ventilation. • Set C088 to the rated motor current. • Select the motor protection under code C119 (I²⋅t monitoring). • Activate the motor protection under code C120. If the motor current permanently exceeds the shown characteristic, fault OC6 is indicated and the controller is inhibited.
8 Display functions 8.1 Code set All codes in the inverter are arranged in different code sets. With factory setting, the standard code set is activated. It contains all codes which are required for the most common applications. By selecting the extended code set under code C000, the display of the keypad also shows those codes which are suitable for special applications. There is also a service code set which is not accessible in general.
8.3 Display of actual values Under codes C050 to C054 you can read different actual values. Code C050 C051 Act. value Output frequency Feedback of PI controller C052 C053 C054 Motor voltage DC bus voltage Motor current 8.4 Display absolute in Hz with C172 = -0-: related to fdmax with C172 = -1-: absolute in Hz absolute in Veff absolute in V absolute in Aeff Switch-on display If you connect the inverter to the mains, the output frequency is shown as the first display (C050).
9 Code table The following table shows which settings you can enter under which codes. For detailed explanations of the codes and their possible functions refer to the corresponding chapters. How to read the code table: Column Code Parameter Acceptance Code C000 C001 C002 C003 C004 C005 C006 Abbreviation C000 C005* -0ON-LINE SH + PRG [SH + PRG] Name Meaning Code of the standard code set Code of the extended code set Factory settings are printed in bold.
Code Name C008 Output signal digital frequency C009* Controller address (only for LECOM) Minimum field 0.
Code Name C025 Preselection: Encoder C026 Constant for C025 C027 C029 C030* C034 C036 C038 C039 C040 C041 C042 C043 C044* C045 Parameter (Factory settings are printed in bold) -1Analog input X1/terminals 1/2 -2Analog input X1/terminals 3/4 -4Analog input X1/terminal 8 -10Digital frequency/incremental encoder input X5 -11Digital frequency/incremental encoder input X8 For analog inputs: xxxx mV factory setting -1000...
Code Name C046 Set-value 1 C048 Enable DC injection braking Display setvalue 2 Output frequency Feedback of PI controller C049 C050 C051 Acceptance see Your page settings ON- LINE 64 SH + PRG 79 x.x% -fdmax to +fdmax 66 x.xHz Actual value 100 x.x%/Hz Actual value Motor voltage DC bus voltage Motor current Fault indication Operating state (only for LECOM) Controller state (only for LECOM) Gain of PI controller x.xV x.xV Actual value Actual value 77, 100 100 100 x.
Code Name C086* Motor frame size C088* Rated motor current C092* C094* Pole pair number (only for LECOM) User password 000 C098 Language C099* Software version Preselection: Additional acceleration and deceleration time (main setvalue) Acceleration time for C100 C100 C101 Parameter (Factory settings are printed in bold) -0Size 71, self-ventilated -1Size 80, self-ventilated -2Size 90, self-ventilated -3Size 100, self-ventilated -4Size 112, self-ventilated -5Size 132, self-ventilated -6Size 160
Code C108 C109 C110 C111 C112 C113 C114 Parameter (Factory settings are printed in bold) Gain for C110 1.00 -10.00...+10.00 (in steps of 0.01) Offset for 0mV -1000...
Code C161C168 Parameter (Factory settings are printed in bold) Preselection: -0Digital input TRIP set Monitoring -1PTC input -15Inverter overload (I ⋅ t monitoring) -16Motor overload (I2 ⋅ t monitoring) Function for For C119 = -0-.
Code C210* C211* C212* C213* C214* C220 C221 C234* C238 C239 C240 C241 C249* C370* C380 C381 C382 108 Name Parameter (Factory setting printed in bold) Preselection: -1Process step 1 Process step -2Process step 2 ... ... -8Process step 8 Set-value for -0Set-value 1 (C046) C210 -1JOG 1 -2JOG 2 ... ... -15JOG 15 Pair of ramp -0Standard pair of ramp times times for C210 (C012 and C013) -1Additional pair of ramp times 1 -2Additional pair of ramp times 2 ... ...
10 Serial interfaces The frequency inverters can communicate with superimposed hosts (PLC and PC) and the Lenze operating units 323 and 324 via the serial interfaces LECOM1 and LECOM2. 10.1 LECOM1 interface X6 The LECOM1 interface (X6 connector) can be used to connect devices to the RS232C standard (LECOM-A) or to the RS485 standard (LECOM-B). The interface is suitable for parameter setting, monitoring, diagnosis, and simple controls.
10.2 LECOM2 interface (option) For more sophisticated applications, you can use a field bus connecting interface. In the programming section, this interface is called LECOM2. For the bus system Interbus-S the connecting interface 2110 with the DRIVECOM profile is available. For the bus system PROFIBUS the connecting module 2130 is also available with DRIVECOM profile. The modules 2110 and 2130 are available are options and can be integrated into the inverter (see also page 50). 10.
10.3.5 Baud rate (LECOM1) Under code C125 you can enter different baud rates. Code C125 Parameter -0-1-2-3- Meaning 9600 baud 4800 baud 2400 baud 1200 baud 10.3.6 History of reset faults Under C161 to C168 you can read the last eight faults stored. The last reset fault is displayed in C161. 10.3.7 Code bank (LECOM1) With version 1.0 of the LECOM A/B protocol, codes up to C255 can be processed. To reach also higher numbers with this version, the accessible range can be changed by code C249.
10.3.9 High resolution data Under codes C380 to C382 you can enter very precise set-value and feedback with a resolution of 14 bit plus sign. Set-value 1: Set-value scaled to the maximum frequency. The value of 214 corresponds to 100% of the maximum field frequency. The information is identical with that under C046, with the difference that you can read the controller value directly thus excluding conversion errors.
10.4 Attribute table If you want to write programs yourself, the following table gives you information for the serial communication via LECOM1 (LECOMA/B) or LECOM2. Legend Code Code DS Meaning Lenze code number Data structure E= Single variable (only one parameter element) A= Array variable (several parameter elements can be selected by the code for the preselection or by LECOM sub code). I= P/S DT DL LCM-R/W LCM1-Form.
114 Code DS P/S DT DE DL LCM-R/W C000 C001 C002 C003 C004 C005 C006 C008 C009 C010 C011 C012 C013 C014 C015 C016 C017 C018 C019 C020 C021 C022 C025 C026 C027 C029 C030 C034 C036 C038 C039 C040 C041 C042 C043 C044 C045 C046 C048 C049 C050 C051 C052 C053 C054 C067 C068 C069 C070 C071 C074 C079 C080 C081 C086 C088 C092 C093 C094 E E E E E E E E E E E E E E E E E E E E E E E I I E E E E E A E E E E E E I E E E I E E E E E E E E E E E E E E E E E P P P P P P P P P P P P P P P P P P P P P P P P P P P P
Code DS P/S DT DE DL LCM-R/W C098 C099 C100 C101 C103 C105 C107 C108 C109 C110 C111 C112 C113 C114 C115 C116 C117 C118 C119 C120 C125 C130 C131 C132 C134 C142 C143 C160 C161 C162 C163 C164 C165 C166 C167 C168 C172 C176 C210 C211 C212 C213 C214 C220 C221 C234 C238 C239 C240 C241 C249 C370 C380 C381 C382 E E E A A E E A A E A E A A A E A A E I E E E E E E E E E E E E E E E E E E E A A A A E E E E E E E E E E E E P P P P P P P P P P P P P P P P P P P P P S S S P P P S P P P P P P P P P P P P P P P P P
116
Service 1 Fault indication When a fault occurs, the operation of the frequency inverter is immediately interrupted and the signal "ready" is removed. The fault is displayed automatically under C067. The fault indication is flashing as long as the fault has not been reset. Fault reset: Press SH + PRG or activate the input TRIP reset. Reset fault indications are stored. They can be displayed again by selected code C067 and pressing the DOWN-key in the parameter level.
List of fault indications 118 Display on keypad --OC1 Display on host 0 11 OC5 15 OC6 16 OH 50 OH3 53 CEO 61 U15 70 CCr 71 Pr 72 Pr1...
2 Warning A warning is displayed automatically under C067. During a warning the signal "ready" is removed, however, the operation of the frequency inverter is not interrupted. Reset of the warning: Press SH + PRG or activate the input TRIP reset.
4 Checking the power stage The measurements described below are to be carried out only by skilled specialists. Use a digital voltmeter. The measuring values indicate the nominal value. If they are different, there is a defective. 4.1 Checking the mains rectifier Disconnect inverter from the mains and wait until the DC bus has discharged (approx. 3 minutes). You can measure directly at the power terminals. Measurement Diodes in forward direction Diodes in reverse direction 4.
Index A Acceleration time, 72 Additional, 82 Additional, Enabling with control via keypad or LECOM, 83 Additional,Programming, 82 Additional.
E I Electrical installation, 20 EMC directive Purpose, 11 Energy sharing, 34 Extended code set, 99 External fault, 118 I-t monitoring, 97 I0control, 70 I0 set-value, 70 V/f rated frequency, 70 Incremental encoder, 73 Inputs Actual value, 29 analog, 29 digital, 30; 32 Digital frequency/incremental encoder, 27 digital, Changing the functions, 78 digital, factory setting, 78 digital, freely assignable, 78 Set-value 1, 29 Set-value 2, 29 Installation electrical, 20 mechanical, 19 installation altitude, 8 Int
M Magnetizing current control (I0 control), 67 Main set-value Ramp generator, 72 Mains chokes, 40 Advantages, 40 Manufacturer’s declaration, 15 Mechanical installation, 19 Minimum output frequency (minimum field frequency ), 71 Monitor signals, 77 Monitoring Motor temperature, 29 Motor drifting, 77 Motor filter, 43 Advantages, 43 Motor overload, 118 Motor protection, 21; 97 Motor voltage filter, 45 Advantages, 45 N Networking, 50 DRIVECOM profile 21, 50 Interbus-S, 50 LECOM-A/B, 51 LECOM-LI, 51 Noise immun
Q T Quick stop, 58 Technical data general, 8 TRIP, 79 TRIP reset, 79 TRIP set, 79 R Ramp generator Input = 0 (RFG/E=0), 84 Input = 0, Keypad or LECOM, 84 Input = 0, Terminal control, 84 S-shaped characteristic, 93 Stop, keypad or LECOM, 84 Stop, Terminal control, 84 Ramp generator stop Stop, 84 Ready (RDY), 88 relative humidity, 8 Reset Warning, 119 Rest Fault, 117 RFI filters, 48 V V/f characteristic control, 68 V/f characteristic, 68 V/f rated frequency, 68 Voltage boost, 69 W Warning, 119 Reset, 11