Owner manual
103
Code Name Parameter
(Factory settings are printed in bold)
Acceptance see
page
Your
settings
C025 Preselection:
Encoder
-1- Analog input X1/terminals 1/2
-2- Analog input X1/terminals 3/4
-4- Analog input X1/terminal 8
-10- Digital frequency/incremental encoder
input X5
-11- Digital frequency/incremental encoder
input X8
SH + PRG 66,
73
C026 Constant for
C025
For analog inputs:
xxxx mV factory setting
-1000...+1000mV
(in steps of 1mV)
For digital frequency/incremental encoder inputs:
-1- 512 pulses/Hz or increments/revolution
-2- 1024 pulses/Hz or increments/revolution
-3- 2048 pulses/Hz or increments/revolution
-4- 4096 pulses/Hz or increments/revolution
ON-LINE
SH + PRG
66,
73
C027 Adjustment for
C025
For analog inputs:
1.000 -2.500...+2.500
(in steps of 0.001)
For digital frequency/incremental encoder inputs:
1.000 -5.000...+5.000
(in steps of 0.001)
ON-LINE 66,
73
C029 Auto-adjustm.
for feedback of
PI controller
-1- Activate auto-adjustment SH + PRG 75
C030* Constant for
digital
frequency
output X9
-1- 512 pulses/Hz
-2- 1024 pulses/Hz
-3- 2048 pulses/Hz
-4- 4096 pulses/Hz
SH + PRG 90
C034 Master current -0- 0...20mA
-1- 4...20mA
SH + PRG 64
C036 Voltage for DC
injection
braking
0.0% 0...40%
(in steps of 0.1%)
ON-LINE 79
C038 Preselection:
JOG
frequency
-1- JOG 1
-2- JOG 2
... ...
-15- JOG 15
SH + PRG 80
C039 Set-value for
C038
50.0Hz -480...+480 Hz
(in steps of 0.1 Hz from 0.0 to 100 Hz
in steps of 1 Hz from 100 to 480 Hz)
ON-LINE 80
C040 Controller
enable
-0- Controller inhibit
-1- Controller enable
SH + PRG 58
C041 Direction of
rotation
-0- Main set-value not changed
-1- Main set-value inverted/invert
SH + PRG 58
C042 Quick stop -0- Quick stop not active/finish
-1- Quick stop active/activate
SH + PRG 58
C043 TRIP reset
(only for
LECOM)
-0- Reset fault SH + PRG 117
C044* Enable
process
control
-0- Process control inhibited/finish
-1- Process control enabled/start
SH + PRG 84,
94
C045 Enable JOG
frequency
-0- Set-value 1 active/activate
-1- JOG 1 active/activate
... ...
-15- JOG 15 active/activate
SH + PRG 80