Owner manual

104
Code Name Parameter
(Factory settings are printed in bold)
Acceptance see
page
Your
settings
C046 Set-value 1 With relative set-value input
xx% -100%...100% of the
maximum field frequency
(in steps of 0.1%)
With absolute set-value input
xxHz -480...+480Hz
(in steps of 0.01Hz from 0.00 to 100.0Hz
in steps of 0.1Hz from 100.0 to 480Hz)
ON- LINE 64
C048 Enable DC
injection
braking
-0- DC injection braking inhibited/finish
-1- DC injection braking enabled/activate
SH + PRG 79
C049 Display set-
value 2
x.x% -f
dmax
to +f
dmax
66
C050 Output
frequency
x.xHz Actual value 100
C051 Feedback of
PI controller
x.x%/Hz Actual value 77,
100
C052 Motor voltage x.xV Actual value 100
C053 DC bus
voltage
x.xV Actual value 100
C054 Motor current x.xA Actual value 100
C067 Fault
indication
xxx Display of a fault/warning 117
C068 Operating
state (only for
LECOM)
16-bit status information, only readable via LECOM 110
C069 Controller
state (only for
LECOM)
8-bit status information, only readable via LECOM 110
C070 Gain of
PI controller
1.00 0.01... 300
(in steps of 0.01 from 0.01 to 1.00
in steps of 0.1 from 1.0 to 10.0
in steps of 1 from 10 to 300)
ON-LINE 76
C071 Adjustment
time of PI
controller
0.1s 0.0...100s
(in steps of 0.01s from 0.01 to 1.00s
in steps of 0.1 from 1.0 to 10.0s
in steps of 1 from 10 to 100s)
ON-LINE 76
C074 Influence of PI
controller
0.0% 0.0...100%
(in steps of 0.1%)
ON-LINE 74,
75
C079* Oscillation
damping
2.0 2.0...5.0
(in steps of 0.1)
ON-LINE 96
C081* Rated motor
power
-4- 0.25kW
-5- 0.37kW
-6- 0.55kW
-7- 0.75kW
-8- 1.1kW
-9- 1.5kW
-10- 2.2kW
-11- 3.0kW
-12- 4.0kW
-13- 5.5kW
-14- 7.5kW
-15- 11.0kW
-16- 15.0kW
-17- 18.5kW
-18- 22kW
-19- 30kW
-20- 37kW
-21- 45kW
-22- 55kW
-23- 75kW
-24- 90kW
[SH + PRG] 76