10.4 Attribute table
If you want to write programs yourself, the following table gives you
information for the serial communication via LECOM1 (LECOM-
A/B) or LECOM2.
Legend
Code Meaning
Code Lenze code number
DS Data structure
E = Single variable (only one parameter element)
A = Array variable (several parameter elements can be selected by the code for the
preselection or by LECOM sub code).
I = Image variable (several parameter elements can only be selected by the code for
the preselection)
P/S Parameter setting/Control (Combination according to C001)
P = Parameter setting
S = Control
DT Data type
B8 = 1 Byte bit coded
B16 = 2 Byte bit coded
VS = ASCII String
FIX32 = 32-bit value with sign; decimal with four decimal places
Examples:
1.2 = 12000
FIX32-dez
00002EEO
FIX32-hex
-10.45 = -104500
FIX32-dez
FFFE67CC
FIX32-hex
N16 = 16-bit value with sign; 0 = 0; 100% = 2
14
100% = 16384
N16-dez
4000
N16-hex
-50% = -8192
N16-dez
E000
N16-hex
DL Data length in byte
LCM-R/W Access authorization for LECOM
Ra = Reading is always permitted
W = Writing permitted under certain conditions (e.g. operating mode, controller inhibit)
Wa = Writing is always permitted
LCM1-Form. LECOM A/B format (see technical description LECOM A/B)
AIF-PZD High resolution data in automation interface.
Mapping on LECOM2 high resolution channel is possible.
PZD = High resolution data