Owner manual
16
3 Application-specific controller selection
3.1 Applications with extreme overload,
peak torque up to 230% of the rated motor torque
− For applications where very extreme starting and
overload torques are necessary (e.g. presses, drilling
machines).
− The inverter provides 200% of the rated torque for a
maximum of 30s.
In the event of cyclic overload, the ratio of overload
time and cycle time must not exceed 0.2.
− For these applications, the monitoring of the output
current is set to operation with rated power
(factory setting) using the codes C119 and C120
(see page 97)
- Please note that a maximum ambient temperature of
50°C is permissible.
1
1.5
1.2
1.8
2.3
n
n
N
V/f-control
M
M
N
I -control
0
Type Order no. Rated
motor
power
kW
Rated
output
current
A
max.
output
current
A for 30s
Output power
kVA
400V 50Hz 480V 60Hz
Mains
current
A
Power
loss
W
8601 33.8601_E 1.1 3.0 6.0 2.07 2.5 3.0 130
8602 33.8602_E 1.5 3.9 7.8 2.7 3.24 3.9 140
8603 33.8603_E 2.2 5.5 11.0 3.81 4.57 5.5 160
8604 33.8604_E 3.0 7.5 15.0 5.2 6.24 7.0 180
8605 33.8605_E 4.0 9.4 19.0 6.51 7.82 8.8 200
8606 33.8606_E 5.5 13.0 26.0 9.01 10.8 12.0 240
8607 33.8607_E 7.5 16.5 33.0 11.4 13.7 15.0 275
8608 33.8608_E 11.0 23.5 47.0 16.3 19.5 20.5 350
8609 33.8609_E 15.0 32.0 64.0 22.2 26.6 28.5 420
8610 33.8610_E 18.5 39.5 79.0 27.4 32.8 34.5 600
8611 33.8611_E 22.0 47.0 94.0 32.6 39.1 41.0 740
8612 33.8612_E 30.0 60.0 120.0 41.6 49.9 53.0 900
8613 33.8613_E 37.0 75.0 150.0 52.0 62.3 66.0 1050
8614 33.8614_E 45.0 89.0 178.0 61.7 74.0 78.0 1050
8615 33.8615_E 55.0 110.0 220.0 76.2 91.4 96.0 1270