3 Application-specific controller selection
3.1 Applications with extreme overload,
peak torque up to 230% of the rated motor torque
For applications where very extreme starting and
overload torques are necessary (e.g. presses, drilling
machines).
The inverter provides 200% of the rated torque for a
maximum of 30s.
In the event of cyclic overload, the ratio of overload
time and cycle time must not exceed 0.2.
For these applications, the monitoring of the output
current is set to operation with rated power
(factory setting) using the codes C119 and C120
(see page 97)
- Please note that a maximum ambient temperature of
50°C is permissible.
1
1.5
1.2
1.8
2.3
n
n
N
V/f-control
M
M
N
I -control
0
Type Order no. Rated
motor
power
kW
Rated
output
current
A
max.
output
current
A for 30s
Output power
kVA
400V 50Hz 480V 60Hz
Mains
current
A
Power
loss
W
8601 33.8601_E 1.1 3.0 6.0 2.07 2.5 3.0 130
8602 33.8602_E 1.5 3.9 7.8 2.7 3.24 3.9 140
8603 33.8603_E 2.2 5.5 11.0 3.81 4.57 5.5 160
8604 33.8604_E 3.0 7.5 15.0 5.2 6.24 7.0 180
8605 33.8605_E 4.0 9.4 19.0 6.51 7.82 8.8 200
8606 33.8606_E 5.5 13.0 26.0 9.01 10.8 12.0 240
8607 33.8607_E 7.5 16.5 33.0 11.4 13.7 15.0 275
8608 33.8608_E 11.0 23.5 47.0 16.3 19.5 20.5 350
8609 33.8609_E 15.0 32.0 64.0 22.2 26.6 28.5 420
8610 33.8610_E 18.5 39.5 79.0 27.4 32.8 34.5 600
8611 33.8611_E 22.0 47.0 94.0 32.6 39.1 41.0 740
8612 33.8612_E 30.0 60.0 120.0 41.6 49.9 53.0 900
8613 33.8613_E 37.0 75.0 150.0 52.0 62.3 66.0 1050
8614 33.8614_E 45.0 89.0 178.0 61.7 74.0 78.0 1050
8615 33.8615_E 55.0 110.0 220.0 76.2 91.4 96.0 1270