3.2 Applications with high overload,
peak torque up to 170% of the rated motor torque
For applications which require a standard
overload behaviour of an inverter (e.g. general
mechanical engineering, hoists, travelling drives,
calenders).
The inverter provides 150% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload
time and cycle time must not exceed 0.1.
For this application, the monitoring of the output
current is set to operation with increased power
using the codes C119 and C120 (see page 97).
Please note that a maximum ambient temperature
of 45°C is permissible.
Type Order no. Rated
motor
power
kW
Rated
output
current
A
max.
output
current
A for 30s
Output power
kVA
400V 50Hz 480V 60Hz
Mains
current
A
Power
loss
W
8601 33.8601_E 1.5 4.0 6.0 2.77 3.33 4.0 140
8602 33.8602_E 2.2 5.3 7.8 3.67 4.41 5.3 155
8603 33.8603_E 3.0 7.4 11.0 5.13 6.15 7.4 180
8604 33.8604_E 4.0 10.1 15.0 7.0 8.4 9.4 210
8605 33.8605_E 5.5 12.7 19.0 8.8 10.6 11.8 235
8606 33.8606_E 7.5 17.6 26.0 12.2 14.6 16.3 290
8607 33.8607_E 11.0 22.7 33.0 15.7 18.9 20.7 340
8608 33.8608_E 15.0 31.7 47.0 22.0 26.3 28.0 440
8609 33.8609_E 18.5 43.2 64.0 29.9 35.9 38.0 560
8610 33.8610_E 22.0 53.3 79.0 36.9 44.3 47.0 670
8611 33.8611_E 30.0 63.5 94.0 44.0 52.8 55.0 775
8612 33.8612_E 37.0 81.0 120.0 56.1 67.3 71.0 960
8613 33.8613_E 45.0 101.0 150.0 70.0 84.0 84.0 1175
8614 33.8614_E 55.0 120.0 178.0 83.1 99.8 105.0 1375
8615 33.8615_E 75.0 148.0 220.0 103.0 123.0 129.0 1675