Owner manual
18
3.3 Application with medium overload,
peak torque up to 135% of the rated motor torque
− For applications where only small starting and
overload torques are necessary (e.g. ventilators,
pumps).
− The inverter provides 110% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload
time and cycle time must not exceed 0.1.
− For this application, the monitoring of the output
current is set to operation with maximum power
using the codes C119 and C120 (see page 97)
− Please note that a maximum ambient temperature
of 40°C is permissible.
Type Order no. Rated
motor
power
kW
Rated
output
current
A
max.
output
current
A for 30s
Output power
kVA
400V 50Hz 480V 60Hz
Mains
current
A
Power
loss
W
8601 33.8601_E 2.2 5.3 6.0 3.67 4.41 5.3 155
8602 33.8602_E 3.0 7.0 7.8 4.85 5.82 7.0 175
8603 33.8603_E 4.0 9.9 11.0 6.86 8.23 9.2 205
8604 33.8604_E 5.5 12.5 15.0 8.66 10.4 11.6 235
8605 33.8605_E −−−−−−−
8606 33.8606_E 11.0 22.5 26.0 15.6 18.7 20.5 340
8607 33.8607_E −−−−−−−
8608 33.8608_E 18.5 42.3 47.0 29.3 35.2 37.2 550
8609 33.8609_E 22.0 57.6 64.0 39.9 47.9 50.0 710
8610 33.8610_E 30.0 62.0 79.0 43.0 51.5 54.0 760
8611 33.8611_E −−−−−−−
8612 33.8612_E 45.0 95.0 120.0 65.8 79.0 83.0 1110
8613 33.8613_E 55.0 115.0 150.0 79.7 59.6 100.0 1320
8614 33.8614_E 75.0 145.0 178.0 100.5 120.5 125.0 1640
90.0* 160.0* 178.0* 110.9* 133.0 138.0* 1640*
8615 33.8615_E −−−−−−−
* These data are valid for a maximum ambient temperature of 30°C.