3.3 Application with medium overload,
peak torque up to 135% of the rated motor torque
For applications where only small starting and
overload torques are necessary (e.g. ventilators,
pumps).
The inverter provides 110% of the rated torque for
a maximum of 30s.
In the event of cyclic overload, the ratio of overload
time and cycle time must not exceed 0.1.
For this application, the monitoring of the output
current is set to operation with maximum power
using the codes C119 and C120 (see page 97)
Please note that a maximum ambient temperature
of 40°C is permissible.
Type Order no. Rated
motor
power
kW
Rated
output
current
A
max.
output
current
A for 30s
Output power
kVA
400V 50Hz 480V 60Hz
Mains
current
A
Power
loss
W
8601 33.8601_E 2.2 5.3 6.0 3.67 4.41 5.3 155
8602 33.8602_E 3.0 7.0 7.8 4.85 5.82 7.0 175
8603 33.8603_E 4.0 9.9 11.0 6.86 8.23 9.2 205
8604 33.8604_E 5.5 12.5 15.0 8.66 10.4 11.6 235
8605 33.8605_E −−−
8606 33.8606_E 11.0 22.5 26.0 15.6 18.7 20.5 340
8607 33.8607_E −−−
8608 33.8608_E 18.5 42.3 47.0 29.3 35.2 37.2 550
8609 33.8609_E 22.0 57.6 64.0 39.9 47.9 50.0 710
8610 33.8610_E 30.0 62.0 79.0 43.0 51.5 54.0 760
8611 33.8611_E −−−
8612 33.8612_E 45.0 95.0 120.0 65.8 79.0 83.0 1110
8613 33.8613_E 55.0 115.0 150.0 79.7 59.6 100.0 1320
8614 33.8614_E 75.0 145.0 178.0 100.5 120.5 125.0 1640
90.0* 160.0* 178.0* 110.9* 133.0 138.0* 1640*
8615 33.8615_E −−−
* These data are valid for a maximum ambient temperature of 30°C.