6.5 Cable protection
Cable protecting fuses for recommended cross-sections:
Inverter type 8601 - 03 8604, 05 8606, 07 8608, 09
Rated fuse current 16 A 20 A 35 A 50 A
Cable cross-section 2.5 mm
2
or
AWG 13 (12)
4 mm
2
or
AWG 11 (10)
10 mm
2
or
AWG 7 (6)
16 mm
2
or
AWG 5 (4)
Inverter type 8610, 11 8612 8613 8614 8615
Rated fuse current 63 A 100 A 125 A 160 A 200 A
Cable cross-section 25 mm
2
or
AWG 3
50 mm
2
or
AWG 0
50 mm
2
or
AWG 0
95 mm
2
or
AWG 3/0
95 mm
2
or
AWG 3/0
Replace defective fuses only with the specified type and when the
device is disconnected from the mains. All power terminals remain
live up to 3 minutes after mains disconnection!
Instead of cable protection fuses you can also use miniature circuit
breakers (e.g. Siemens type 5SX2, 3.. - 6)