Owner manual

7
Planning
1 Features of the 8600 inverter series
Liability
The information given in these Operating Instructions describe
the features of the products but do not guarantee them.
Power stage
Large mains voltage range: 3 x 330 to 528V AC or
470 to 740V DC
Inverter with IGBTs, protected against short circuits
4kHz chopper frequency, adjustable up to 16kHz
Output frequency up to 480Hz,
V/f rated frequency up to 960Hz
Overload capacity up to 200% rated current for a short time
Overload monitoring can be set
Integrated brake transistor, external brake resistors in IP20
enclosure as option
Connections for DC bus supply
Control stage
Digital control unit with 16-bit microprocessor
Simple parameter setting and diagnosis using keypad and two-
line display in German, English, and French language
Parameter setting during operation
V/f-characteristic control with linear or square characteristic
High breakaway torque by magnetizing current control
Constant speed due to slip compensation
Speed control using DC tacho or incremental encoder
Current limitation with V/f lowering for stall-protected operation
Motor overload monitoring via PTC input or
I
²
t-monitoring
Process control with a maximum of eight steps
Synchronisation coasting motor due to flying restart circuit
Serial interface (RS232C/RS485) for external parameter setting
and operation
Field bus connecting modules as option to be integrated into the
device
Approvals (unit types 8602 to 8611)
VDE 0160, VDE reg.-no. 86694
UL 508, file no. 132659