EDB8600UE-V009 00392929 hze Operating Instructions Inverter Drives 8600 series Varian f Dancer-position control with Torque control
These Operating Instructions are valid for the units with the following nameplate data: 8601 8602 8603 8604 8605 8606 8607 8608 8609 8610 8611 8612 8613 8614 8615 E.6x.6x.V009 E.6x.6x.V009 E.6x.6x.V009 E.6x.6x.V009 E.6x.6x.V009 E.Gx.Gx.VOO9 E.6x.6x.VO09 E.6x.6x.V009 E.6x.6x.V009 E.6x.6x.V009 E.6x.6x.VO09 E.6x.6x.V009 E.6x.6x.VO09 E.6x.6x.VO09 E.6x.6x.
How to use these Operating lnstructions... To locate information on specific topics, simply refer to the table of contents at the beginning and to the index at the end of the Operating Instructions. These Operating Instructions use a series of different Symbols to provide quick reference and to highlight important items. This Symbol refers to items of information intended to facilitate Operation. Notes which should be observed to avoid possible darnage to or destruction of equipment.
General safety in conformity and Operating Instructions with the Low-Voltage 1. General In operation, drive converters, depending on their degree of protection, may have live, uninsulated, and possibly also moving or rotating parts, as well as hot surfaces. In case of inadmissible removal of the required covers, or improper use, wrong installation or maloperation, there is the danger of serious personal injury and damage to property. For further information, see documentation.
Table of contents Planning l Feiatures of the 8600 series variant dancer-Position control 9 2 Technical data 11 2.1 General data 2.2 Dimensions 2.3 Scope of delivery 2.4 Application as directed 2.5 CE conformity 2.51 EC Low-Voltage Directive (73/23/EEC) 2.5.2 Electromagnetit Compatibility (89/336/EEC) 11 3 Application-specific controller 19 selection 3.1 Applications with extreme overload, peak torque up to 230% of the rated motor torque 3.
Accessories 38 6.1 Brake resistors 6.1 .l Selection of the brake resistor 6.1.2 Technical data of brake resistors 6.2 Mains Chokes 6.2.1 Selection of the mains Choke 6.2.2 Technical data of mains Chokes 6.3 Motorfilter 6.3.1 Technical data of motor filters 6.4 Sine filter 6.4.1 Technical data of sine filters 6.5 Gable protection 6.6 RFI filters 6.6.1 Ratings of RFI filters 6.6.2 Technical data of RFI filters 6.
4 Closed-loop speed control 75 4.1 Analog act. value 4.2 Digital act. value 4.3 Frequency Pilot control 4.4 Adjustment of the act. value gain 4.4.1 Automatic adjustment 4.4.2 Manual adjustment 4.5 Setting of the controller Parameters 4.6 Additional functions 75 75 76 78 78 78 79 80 5 Programming of the freely assignable inputs and Outputs 81 5.1 Freely assignable digital inputs 5.2 Functions of the freely assignable digital inputs 5.2.1 Set TRIP 52.2 Reset TRIP 5.2.3 DC-injection brake 5.2.
j .~..,,, ,i _, .,>, :,,. .,,;’ : > ‘., ,‘: ., ,_j _’ : .*‘\ , ;> ,.’ ,b, ,. ,,. ,, i ,‘:,;‘,:: ,_ ^“‘I j< ‘:.:‘.c, : > >, ,, ’ ,’>,>, ,. <. ; : ,>,, ,,>. :‘t;;,;’ , , j < , ,j :. s j ,,’ _,,” ,,,, ,. :. .‘ : : ,‘ : , : ,, ., ; ; : , ,’ ,,, ,, 1 ,:> j : I 0 v>, O, ‘,: ,, I I’ :; , ,” s ‘_ i ,< ,j ,,j ‘, , > >:.<., ,. ,‘I ‘_,i_, : ,:,., “, :.__ ,,, ,,ii’ : > : s’ ,. Ij ; < , > ,, j ,,~ ,’ <> :,,.,>I. * ” _, ,’ :, .‘._‘. ,‘ _: :, ,\ j “”i :>: I,. j, : ‘-’ ~, .,,j _‘; . _,’ >,, ‘,,’ :,<, , ^ >” <’ ‘.
12 Serial intetfaces 12.1 LECOMI interface X6 12.2 LECOM2 interface (Option) 12.3 LECOM Codes 12.3.1 Controller address 12.3.2 Operating state 12.3.3 Controller state 12.3.4 Pole pair number 12.3.5 Baud rate (LECOMl) 12.3.6 History of reset faults 12.3.7 Code bank (LECOMI) 12.3.8 Enable automation interface (LECOM2) 12.3.9 High resolution data 12.4 Attribute table Service 1 Fault indication 2 Warning 3 Monitoring 4 Checking the power Stage 4.1 Checking the mains rectifier 4.2 Checking the power Stage 4.
lenze
Planning 1 Features of the 8600 series variant dancer-Position control In addition to numerous Standard functions, this variant offers various functions which are required for a dancer-Position control used for winding applications. Another possibility is to activate a torque control. For more detailed information about the special functions see chapters 9 and 10. Power Stage l Wide mains voltage range: 3 x 330 to 528V AC or 470 to 740V DC l Controllers with IGBTs, protected against short circuits .
SpeciaI l functions Dancer-Position controller with speed and diameter evaluation l Diameter detection via analog input l Soft insertion of the dancer-Position controller via ramp function generator or multiplication with the main setpoint l Sensor compensator for fault and diameter corrections l Torque control with Speed limitation Approvals (types 8602 to 8611) + VDE 0160, VDE reg.-no. 86694 l UL 508, file no.
2 Technical data 2.1 General data Mains voltage: Output voltage: Output frequency: Chopper frequency: Threshold of the integrated brake chopper Enclosure: Ambient temperature: Noise immun@ Permissible pollution 3 x 46OV AC, 45 to 65 Hz Permissible voltage range: 330...526 V (as alternative: 470...740\1 DC supply) 3 X 0 t0 Vmains (V - fd with 400V at 50Hz, adjustable, mains-independent) When using a mains Choke, the maximum possible output voltage is reduced to approx. 96% of the mains voltage.
2.2 Dimensions a Bottom 2.3 view Scope of delivery The scope of delivery includes: 0 frequency controller type 86XX-E 0 setpoint l l 12 Potentiometer accessory kit incl.
2.4 - Application as directed The 8200 series consists of electrical devices which are designed for application in industrial power installations. The controllers are directed - as components for the control of variable Speed drives with AC motors - for the installation into control cabinets or control boxes - as controllers for the installation of drive Systems The controllers comply with the protection requirements of the EC Low-Voltage Directive.
2.5 CE conformity What is the purpose of EC directives? EC directives are issued by the European Council and are intended for the determination of common technical requirements (harmonization) and cet-tification procedures within the European Community. At the moment, there are 21 EC directives of product ranges. The directives are or will be conver-ted to national laws of the member states.
- 2.5.
2.5.2 EC Declaration of Conformity ‘95 for the purpose of the EC Directive relating to Electromagnetit Compatibility (89/336/EEC) amended by: First amended directive (92/31/EEC) CE mark directive (93/68/EEC) The controllers of the 8600 series cannot be driven in stand-alone Operation for the purpose of the regulation about electromagnetic compatibility (EMVG of 09/11/92 and 1st EMVGÄndG - amended directive - of 30/08/95). The EMC tan only be checked when integrating the controller into a drive System.
Considered basic Standards for the test of noise immunity: - Hameln, 27/11/1995 . . .4 . . . .. . . . . . . . . . --l/. . . . . I. . . . . . . . i. V. (Lang&) ProdudManager d lenze /’ * . . . . . .d...............................
2.5.
- 3 Application-specific controller selection 3.1 Applications with extreme overload, peak torque up to 230% of the rated motor torque -- For applications where a very extreme starting and overload torque are necessary (e.g. presses, drilling machines). r - The controller provides 200% of the rated torque for a maximum of 30s. With cyclic overload, the ratio between overload to cycle time must not exceed 0.2.
3.2 Applications with high overload, peak torque up to 170 % of the rated motor torque - For applications which require a Standard overload behaviour of a controller (e.g. general mechanical engineering, hoists, travelling drives, calenders). ~~ M,Mt lncontrol - The controller provides 150% of the rated torque for a maximum of 30s. For cyclic overload, the ratio overload to cycle time must not exceed 0.1.
3.3 Applications with medium overload, peak torque up to 135 % of the rated motor torque - For applications where only a small starting and overload torque are necessary (e.g. Ventilators, w-w+ - The controller provides 110% of the rated torque for a maximum of 30s. For cyclic overload, the ratio overload to cycle time must not exceed 0.1.
4 Handling 4.1 Mechanical installation These frequency controllers must only be used as built-in units. Install the controller vettically with the terminal Strips at the bottom. Allow a free space of 100mm at the top and bottom. For the controllers 8612 . . . 8615 this free space must also be allowed at both sides. Ensure unimpeded Ventilation of cooling air.
4.2 l l l l - Electrical installation The Controllers contain sensitive electrostatic compontents. Priior to assembly and Service operations in the area of the controller connections, the Personne1 must be free of electrostatic Charge. These persons tan discharge themselves by touching the PE fixing screw or another grounded metal part in the control cabinet. All control inputs and Outputs of the controller are mainsisolated. The mains isolation has a basic insulation.
4.2.1 Motor protection The units do not have a full motor protection. For monitoring the motor temperature PTCs orthermal contacts tan be used. The connection possibilities are shown on page 28. - When using group drives, a motor protection relay is required for each motor. When using motors which do not have a suitable insulation for controller Operation: - Connect motor filters for protection (see page 45). Please contact your motor manufacturer.
4.2.3 CE-typical drive System - - Components of the CE-typical drive sytem Controller, RFI filter and mains Choke are mounted on one assembly board. The System components are functionally wired according to the chapter 5, section: Planning of the Operating Instructions. Installation of CE-typical drive Systems The electromagnetic compatibility of a machine depends on the method and accuracy of the installation. Special care must be taken of: l l l filters, screens and grounding.
Installation l 9 l Connect the Controller, mains fitter, and mains Choke to the grounded mounting plate. Zinc-coated mounting plates allow a permanent contact. If the mounting plates are painted, the paint must be removed in every case. - When using several mounting plates they must be connected with as large surface as possible (e-g. using topper bands). Connect the Screen of the motor cable to the Screen connection of the Controller and to the mounting plate of a surface as large as possible.
Part of the CE-typical drive System on mounting plate Ll LZ L3 Connection mains fuse Paint-free bare metal ^^^A^_, -...a---I, contact surfaces Ill -. Conductive connection between mounting plate and PE connection Cables between mains filter and controller longer than 0.3 m n.mmn,TA must be screened /’ c’ ,, 6.’I /’ Screened control cables Screened motor cable, connect Screen to PE also at the motor side, l a r g e cross-section contact to the motor housing required - 4.2.
5 Wiring 5.
5.1.1 Tightening torques of the power terminals Type 8601...8605 0.6...0.8 Nm (5.3...7.1 Ibfin) Tightening torque 5.2 8606,8607 8608...8611 8612,8613 1.2...1.5 Nm 1.5...1.8 Nm 6...8 Nm (10.6...13.3 Ibfin) (13.3...16 Ibfin) (53,..70Ibfin) 8614,8615 15...20 Nm (133...
52.1 Analog inputs and Outputs PA R > 2.2k (unipolar setpoint) (bipolar setpoint) Setpoint 2 Feedback Setpoint Monitor 1 Outputs 5.2.
5.2.3 Description of the analog inputs and Outputs Analog inputs -~ -erminal Switch setting Use (factory setting) 1Setpoint LevellResolution Parameter setting see -3ov...+3ov 12bit + sign 75, 68 2 i 2bit + sign s, -12ov...+12ov 75.68 -1 OV/7mA - Level Parameter setting see Page - Monitor 1 (Output frequency) -1ov...+1ov 94 Monitor 1 (output frequency) -2OmA...+20mA 94 Monitor 2 (output current) -1ov...+1ov 94 Monitor 2 (output current) -2OmA...
5.2.5 Digital inputs and Outputs The functions for the digital inputs and Outputs shown below are factory-set. To switch the Signal cables, only use relays with lowcurrent contacts. Relays with gold-plated contacts have proven for this. - All digital inputs and Outputs are PLC compatible and are - when operated with an external voltage supply (24 V) - isolated from the rest of the control Stage. To connect the voltage supply, use terminals 39 and 59.
Internal voltage supply (1 - 5V) Inputs: Input voltage: 0 to 30 v LOW Signal: oto5v HIGH Signal: 13to30v for 15 V 5 mA per input Input current: Outputs: Maximum voltage supply: Maximum output current: 30 v 50 mA per output external resistor at least 300 0 for 5 V, e.g. relay patt no. 326 850) GND ext. - *+ Ctr. enable DC-inj. brake TRIPJOG SetlReset Caution: lenze TRIP Ti Pulse inhibit Imax RDY Qmin RFG/O=I The internal 15 V supply may be loaded with a maximum of 100 mA.
5.2.
52.7 Frequency output 6. fd If you want to display, for example, the output frequency or the speed of the drive via a digital display device, you tan use the frequency output “6 times field frequency”. As factory setting, this function k assigned to terminal A4. This output is, like the other digital Outputs, isolated and tan be supplied via terminals 39 and 59.
5.3 Operation with DC-bus supply 5.3.1 Connection of several drives Drives which are supplied by a three-phase voltage tan also be linked via the terminals +UG and -UG for energy-sharing. This type of connection requires all controllers to be supplied simultaneously with the same mains voltage, with each controller being connected to the recommended mains Choke. further contr. - * The fuses must be dimensioned for the rated output current of the device and a voltage strength of 1000 V DC. 5.3.
5.4 Screenings - Cable screenings increase the noise immunity of the drive System and reduce the interfering radiation. The power and control terminals of the controllers are noise immune without screened cables up to severity class 4 to IEC 801-4. Burst of 4kV on the power terminals and 2kV on the control terminals are permissible. Screenings are only required when you want to operate the controller in environments, where severity class 4 is not sufficient.
6 Accessories Accessories are not included in the scope of supply. 6.1 Wake resistors In the generator mode, e.g. when decelerating the drive, the machine returns energy to the DC bus of the controller. If large inertias are braked and/or short deceleration times are set, the DC bus voltage may exceed its maximum permissible value. In the case of overvoltage in the DC bus, the controller sets pulse inhibit and indicates “overvoltage “.
6.1 .l Selection of the brake resistor l l The following combinations ensure - a maximum braking time of 15 seconds - a maximum relative duty time of 10%. The set continuous power of the controller is the reference for the combination. Operation at rated power (factory setting) 8602 8603 8604 8605 370 240 180 0.15 0.2 0.3 ERBM370R150W ERBM370R150W ERBM240R200W ERBDl80R300W 8607 8608 8609 100 68 47 0.6 0.8 1.2 ERBDlOOR600W ERBDlOOR600W ERBD068R800W ERBD047ROl K ERBD033R02KO 180 0.
. If the above conditions do not apply, you tan determine the suitable brake resistor as follows: 1. Determine the resistance: Resistance [Q] 2 required brake peak power Depending on the unit the resistances must not fall below the following values: Controller type 18601 18602 18603 18604 18605 18606 18607 Min. resistancet 118OD Il8OC2 1180C2 [18Ot2 1180R IIOOR IIOOQ Controller type 18608 18609 18610 18611 18612 18613 18614 18615 Min.
6.1.2 Technical data of brake resistors All listed brake resistors are equipped with an integrated temperature monitoring. The brake contact which is switched in the event of overtemperature is designed for: l l max. 250 V AC max. 0.
Moulded module resistors on heatsink I , ,k-i I d b Brake resistor Resistance Order number a b mm mm Dimensions d mm e mm Cl mm C 370 ERBM370R15OW 80 240 70 225 95 5 k mm 7.5 240 ERBM240R200W 80 340 70 325 70 5 7.5 Brake resistor Resistance Order number n 370 240 6.2 a mm ERBM370R15OW ERBM240R200W Power kW 0.15 0.2 Resistor values Peak brake power kW 1.4 2.
6.2.1 Selection of the mains Choke l Thie set permanent power of the controller is the reference the combination. for Operation at rated power (factory setting) 8602 3.9 8603 5.5 8604 7.0 8605 ELN3-0250H007 3 x 2.5 7.0 ELN3-0250H007 3 x 2.5 7.0 ELN3-0250Ho07 3 x 1.6 12.0 ELN30160Ho12 3x 1.6 12.0 ELN3-ol6oHol2 ELN3-0120H017 8607 15.0 3x 1.2 17.0 ELN3-0120H017 8608 20.5 3xl.2 25 ELN3-0120H025 8609 28.0 3 x 0.88 35 ELN3-0088H035 8610 34.5 3 x 0.75 45 ELN3-0075H045 8612 53.0 8613 66.
6.2.2 Technical data of mains Chokes k b-4 Mains Choke i’A / 2.5mH 12A/ 1.6mH 17A/1.2mH 2 5 A / 1.2mH 3 5 A / 0.88mH 4 5 A / 0.75mH 55A/0,88mH 85A / 0.38mH Order no. ELN3-0250HOO7 ELN3-0160H012 ELNS-0120H017 ELN3-0120H025 ELN3-0088H035 ELN3-0075HO45 ELN3-0088H055 ELN3-0038HO85 105A / 0.27mH ELN3-0027H105 130A / 0.
6.3 Motor filter .-. Advantages of using a motor filter: . l The motor filter reduces capacitive currents caused by parasitic cable capacitances. The slope of the motor voltage (dv/dt) is limited to 500 V/ps. Motorfilters are always required for: l unscreened cables langer than 1 OOm. l screened cables longer than 50m. o when using motors which do not have suitable insulation for controller Operation. (Observe data of the motor manufacturer.
6.3.1 Technical data of motor filters e 4 Design A a Design B With motor currents z 55 A please use motor filters which are connected in parallel.
6.4 Sine filter - Advantages of using a sine filter: l Sinusoidal output voltages to supply electronie devices. Please note: l l l L l l l - Irrstall the sine filter as close as possibie to the controller. Select the control mode “V/f-characteristic control” (COO6=-0-). The “magnetizing-current control” form of control is not permissibie. The chopper frequency must be set to 8 kHz (CO1 8 = -4-). The controller is loaded additionally with approximately 10% of the rated current of the sine filter.
6.4.1 Technical data of sine filters l - d -~- a I b Al Design A Design B If you need a sine filter for higher currents, please contact the factory.
6.5 Gable protection Cable protecting fuses for recommended Cross-sections: Controller type Rated fuse current Cable Cross-sectlon 8601 - 03 16A 2.
RFI filters 6.6 Advantage of using a RFI filter: Reduction of high-frequent radio interference. l Please note: Because of the generation of leakage currents, the RFI filters must be connected to earth. The RFI filter must always be connected to earth at first even if you only want to test the System. Otherwise, the System is not protected against shock. l l The filters listed in the following tan be connected to the 400 V mains.
6.6.2 Technical data of RFI filters a Design A - E Design B Filter type Design Rated current A 8.OA A 16.OA 2 5. O A - 6.7 l l - l l Order EZF3-008A001 EZFB-016AOOl 1EZF3-025AOOl number mm a mm b mm c d mm e mm f mm g mm 220 240 115 150 100 135 180 200 60 65 17 17 115 115 m mm 6.5 6.5 Weight kg 1.8 1.8 1 250 1 150 1 135 1 200 1 65 1 17 1 115 16.5 ( 3.
7 Accessories for networking We will be pleased to send you futther information detailing these accessories on request. - Connecting module 21 lOlB- Interßus-S 7.1 Features: . Additional module for the Lenze series 4900, 8600, 9200 . Slave connection module for the communication System InterBus-S . Can be integrated into the base controllers . Can be combined with the automation modules 2211 PP, 2212WP . Patticipants of peripheral bus in the InterBus-S System .
7.3 Connecting elements for Optical fibre cables-LECOM-LI Lenze offer a series of specially designed connection accessories for the controllers, in Order to use the fibre optic communication bus. The accessories included adapters with Optical transmitter and receiver, a distributor and power pack. Due to the Optical fibre cables, data transmission with a very high immunity to interferences is possible. 7.
8 Initial switch on - Which settings are necessary for the drive to operate? After mains connection the controller is ready to operate after approx. 0.5 seconds. The frequency controllers are factory-set such that a four-pole Standard motor with 400V rated voltage and 50Hz according to the combinations in section 3.1 tan be operated without further settings. In case of motor ratings according to section 3.2 or 3.3, page 17ff, it is necessary to increase the permanent output power accordingly.
Parameter setting 1 Keypad Plain text display Display of Status: Fieady for Operation (LED green) Imax-limit reached (LED red) Pulse inhibit (LED yellow), released by: - Controller inhibit - Fault indication (TRIP) - Undervoltage/overvoltage Keys 1.
2 Basic Parameter setting Programming of the frequency controller enables the drive to be adapted to your application. The possible settings are arranged in Codes, which are numbered in ascending Order and statt with the letter “C”. Esch code provides one Parameter which tan be selected according to the application. Parameters tan be absolute or relative values of a physical unit (e.g. 50Hz or 50% related to fdmax) or numerical Codes giving certain Status information (e.g.
The arrow Position marks whether you are in the code or in the Parameter level. v Press, until CO1 1 is displayed + C ‘0 a. ‘1 x ‘1 ’ EL ” ’ m f ’ ’ ‘5 ‘0 ‘. ‘0 ’ ‘H ‘z ’ ‘r ‘e lq 1~ Ie In Ic ly 1 1 Press PRG to Change to the Parameter level f ’ -3 ’ ‘r ‘e ’ 5 ‘0 ‘q ‘u ‘. ‘0 ‘e ‘n ’ ‘H ‘z ‘c ‘y ’ ’ ’ APress, until 60 Hz is displayed m - C’O’l a x IE’ ‘1 ” ’ ’ f ’ -3 ’ ‘r ‘e ’ 6 ‘0 1.
2.1 .l Parameter setting by two Codes Some Parameters are set by two Codes. A preselection code is used to select the Parameter which is to be changed. The Parameter is then changed by another Code. For example, to set the JOG frequency JOG3, first set the preselection code CO38 to -3- and then set the desired frequency for JOG3 via code C039. 2.2 Save Parameters After the acceptance, new Parameters are saved in the RAM until the controller is connected to mains voltage.
3 Basic settings 3.1 Operating mode The controllers of the 8600 series offer different interfaces. From these you tan select each one for control and programming. Controller interfaces for control and programming: Terminals The terminals are exclusively used to control the controller. Keyp’ad The five keys and the plain text display tan be used mainly for programming. A control via the keypad is also possible.
3.1 .l Controller enable Depending on the selected operating mode (Cool) different procedures are necessary to enable the controller. - Terminal control, i.e. CO01 = -O-, -2-, -4l l Apply a voltage between 13 and 30V across terminal 28. If you have pressed the STP key, enable the controller with SH + STP in addition. In case of terminal control, CO40 serves as a display: l CO40 = -0- means controller is inhibited. l CO40 = -l- means controller is enabled. Control via keypad, i.e.
_- In case of control via the keypad or the LECOM interface, quick stop tan also be (de-)activated via C042. Parameter (Factory setting is printed in bold) -oQuick stop not active/deactivate quick stop -lQuick stop activelactivate quick stop Acceptance SH + PRG If you want to deactivate quick stop: . l - Apply a voltage between 13 and 30V across terminals 21 or 22 (CCW rotation). If you have set CO42 to -l- via the keypad or one of the L.
3.2 Configuration Using code CO05 you tan determine the internal control structure and the use of the setpoint and act. value inputs.
3.2.1 Example of how to select a configuration The direction of rotation of the motor in a System is to be determined by the sign of the analog setpoint (O...+iOV for CW rotating field, O...lOV for CCW rotating field). A closed-loop Speed control is to be used, for which a DC tacho serves as act. value. A setpoint 2 is not used.
Signal-flow Chart for Speed-controlled Operation (CO05 = -o-t0 -15) Keypad, LECOM (na bt Co05 = -2-. -14-. -15) I Jd T .’ Digital frequency (X5 -2.1 _ 5-)Keypad. / LECOM Digital frequency iT$ I - -Co05 Configun S c a l i n g Gatn t” fdmax Ilm C CO3 J JOG frcquenci 15.-1 O Saling tn ‘dmax free digttal input Scaling Gain to f dmax -1 Direction of rotation digital inputs ,nternal change-wer 0% 1 Cl, - -0. F- Co05 -7 -1.. 6’ -1...
Ramp generator for quick stop 1 Ramp generator output = ramp generator invut & Deceleration time Ramp generator output = Ramp generator input M Keypad, LECOM bb - Total setpoint - Frequency Pilot control ‘% enable.
3.4 Features of setpoint 1 An analog entry of setpoint 1 is possible via input Xl/terminal 8, otherwise it is entered via the keypad or the LECOM interfaces. This depends on the selected operating mode (Cool). The configuration determines whether the input is unipolar, bipolar, or independently of the operating mode, a digital frequency input. With terminal control you tan read setpoint 1 under code C046.
3.4.2 Digital frequency input - With the corresponding configuration (CO05) you tan use the g-pole Sub-D socket X5 or X8 as digital frequency input, where two complementary Signals shifted by 90” are provided. If you use an HTL-encoder, it is sufficient to provide only the Signals A and B. The inputs A\ and B\ must then be bridged using +Vcc (pin 4). The maximum input frequency is 300 kHz for TTL encoders and 100 kHz for HTL encoders.
Features of setpoint 2 3.5 Setpoint 2 tan only be provided via the differential input Xl/terminals 1,2, independently of the selected operating mode (Cool). Its value tan only be displayed in per cent under code co49. - Setpoint 2 is processed first by a special ramp generator, before it is added to setpoint 1 .The ramp times of the ramp generator are set separately via C220 and C221.
Gain Set the Signal gain after the offset adjustment. First apply that Signal to which you want to adjust the internal display (see offset). Then select under CO25 the corresponding analog input. Adjust the Signal gain such that the desired setpoint is obtained. For the adjustment of the act. value see pages 75 and 77.
The Io control, also referred to a “magnetizing-current control” allows a considerabiy higher torque compared to the normal V/fcharacteristic control, without the motor being overexcited when the drive is deloaded. 3.7.1 V/f-characteristic control You have to Change from Io control (factory setiing) to V/fcharacteristic control if you want to supply several drives with different loads or rated power from one controller.
-. Vif-rated frequency With the V/f-rated frequency, the slope of the characteristic is set. The value to be entered under CO1 5 results from the motor ratings: V / f -- rated frequency = 400 v VNmotor . rated motor frequency The values for the most common motor types tan be obtained from the following table. Motor data rated voltage 380V 4oov I t k - 4 1 5 v 415v 440v 460V 4aov 4aov rated frequency 50Hz V/f-rated frequency (C015) 52.6Hz 50Hz 50Hz 60Hz 60Hz 50.OHz 48.2Hz 57.8Hz 54.
3.7.2 IO contra1 “Io control” is especially suited for machines with a large breakaway torque. Compared to the V/f-characteristic control it provides considerably larger torques up to the motor rated Point. The advantages of IO control tan be used especially for Single drives. lt is also possible for group drives, provided that the motors are of the same type and have the same load, e.g. two identical drives, which drive a common shaft from two sides.
3.8 Minimum field freqUenCy fdmin You tan use Code CO10 to program a minimum output frequency. This changes the influence of the analog setpoint to setpoint 1 in the factory-set configuration CO05 = -0- (not for other configurations). Setpoint 1 / - 100% 1. ,analog setpoint XlAerm. 8 For fsetpoint inputs via keypad or LECOM interfaces, the fdmin setting is not effective. Parameter (Factory setting is printed in bold) Name Acceptance 0.0 Hz (0.
3.10 Acceleration and deceleration times Tir, Tlf The ramp generators (main setpoint, setpoint 2) are programmed using the acceleration and deceleration times. Under CO12 and CO1 3, the ramp generator for the main setpoint (Setpoint l/JOG frequency) receives its Standard setting. The acceleration and deceleration times refer to a Change of the field frequency from 0 to the maximum field frequency set under CO1 1.
4 - Closed-loop speed control For a number of applications, the accuracy which tan be obtained with open-loop Speed control is often not sufficient. To avoid a Speed reduction which occurs when an asynchronous motor is loaded, you tan select a configuration with a Pl controller. The appropriate configuration depends on the way of setpoint input and the actual value input you want to use.
Code Name CO26 Constant CO25 for Parameter (Factory setting is printed in bold) CO25 = -1 -, -2-, -4(preselection of the analog inputs): xxxx mV factory setting -1000 mV +lOOO 11 mv) Acceptance ON-LINE - mV CO25 = -1 o-, -ll(preselection of the digital-frequency inputskcremental encoder inputs): -l512 pulse/Hz or incrementskevolution -2. 1024 pulse/Hz or increments/revolution -3-4- 2048 pulse/Hz or incrementslrevolution 4096 pulse/Hz or incrementskevolution Adjustment for CO25 = -l-, -2.
M t Torque characteristic of the motor Stationary Operation Setpoint = act. value Output frequency -~~.~-~ Pilot control of set-value/feedback - Pt controjter Signal Closed-loop control without Pilot control, closed-loop control of an application datum The Pl controller is normally used for the Speed control of the connected motor. The large setting ranges of the control Parameters also allow the control of an application datum if this depends on the drive Speed.
4.4 Adjustment of the act. value gain If you use an incremental encoder for Speed control and you have entered the encoder constant as described under 4.2. (see page Fehler! Textmarke nicht definiert.) an adjustment of the act. value gain is not necessary. For tacho act. value, a gain adjustment is normally required. 4.4.1 Automatic adjustment To adjust the act. value gain you tan activate an automatic adjustment under C029.
Calculate the required act. value gain according to the following equation: l --. Required gain = active gain l measured Speed desired Speed Enter the calculated value after selecting the suitable act. value input (C025) under C027. 4.5 Setting of the controller Parameters With the setting of the Controller Parameters, you adapt the Pl Controller to the drive. This adjustment is necessary after the autoadjustment as well as after the manual adjustment.
4.6 Additional functions For special applications, you tan use a variety of additional functions: - Input integral action component = 0 Using this function, the integral action component (I-component) of the PI controller tan be reset to zero. You tan activate this additional function via one of the freely assignable digital inputs. Fur further information about programming of the freely assignable inputs see page 81. This function is e.g.
5 Programming of the freely assignable inputs and Outputs Most of the inputs and outputs of the frequency controller are freely assignable via their own Codes, i.e. they tan be especially assigned to the required Signals. Furthermore, these Signals tan be adjusted in the best possible way by setting facilities. In factory setting, these inputs are already assigned to certain functions. Freely assignable digital inputs 5.
[ C o d e IName 1Parameter (Factoty setting is printed in bold) Acceptance Function tan be changed via CO01 [SH + PRG] Function tan be activated via terminals indeoendentlv at CO01 Except for the functions “Enable JOG frequencies”, “Enable additional acceleration and decleration times” and “Select Parameter Set”, every function tan only be assigned to one terminal. If you want to re-assign an input, the previous programming is lost. A function tan only be assigned to one input.
5.2.3 DGinjection brake If you want to brake the drive fast, but do not want to use a brake chopper, you tan activate the DC-injection brake via the suitable input. Please note that the braking time may vary each time. Before you tan use the DGinjection brake, set the brake voltage under C036. The brake voltage also determines the brake current and therefore the brake torque. If the current limitation is activated by the brake current, reduce the brake voltage.
5.2.4 JOG frequencies If you need cer-tain fixed settings as main setpoint, you tan cal1 programmed setpoints via the JOG frequencies. These JOG frequencies replace setpoint 1. Please note that in configurations with additional setpoints, the setpoint 2 is set to zero, as long as a JOG frequency is active.
Enabling JOG frequencies With terminal control activate the assigned digital inputs according to the table below. The input with the smallest number is the first input, the input with the next highest number is the second input, etc. (e.g. E4 = first input, E5 = second input). With terminal control, the active JOG frequency is displayed under co4.5. With control via keypad or LECOM interfaces activate the JOG frequencies.
5.2.5 Additional acceleration and deceleration times For the ramp generator of the main setpoint (setpoint l/JOG frequency) you tan cal1 additonal acceleration and deceleration times from the memory, e.g. to Change the acceleration Speed of the drive as from a certain Speed. Programming of additional acceleration and deceleration times The ramp times are set in two Steps, under ClOO, one pair of acceleration and deceleration times is selected.
Enabling the additional acceleration and deceleration times With terminal control activate the assigned digital inputs according to the table below. v0 1 A’ r’ ---1 The input with the smallest number is the first input, the input with the next highest number is the second input, etc. (e.g. Ei7 = first input, E8 = second input). 1st i n p u t 2nd 1 0 1 -E -LA T,t9 ) TlJ2, Ti,1 T,J3, Ti,lO, T,tlO 1.T,r7, T,t7 Tl& Tir6, T,t6 Titl2 Titl3 Ti18 T,fll T 14, T,t14 LL 1 T,,15.
5.2.6 Ramp generator stop While the drive is accelerated via the ramp generator of the main setpoint, you tan hold the ramp generator using the assigned digital input, e.g. to wait for cet-tain actions before accelerating. With terminal control you tan read under Cl31 whether the ramp generator is stopped or not. With control via the keypad or the LECOM interfaces the ramp generator (main setpoint) is stopped and enabled again under C131.
- 5.2.9 You tan store up to four different Parameter Sets, for example when you want to process different material with one machine or if you want to run different motors with one controller. Programming of Parameter sets To program several Parameter Sets, the following Steps are requ ired: l l l Enter all settings for one application. Select code CO03 and save your Parameter set for example under -l- (Parameter set 1). Enter all settings for another application (e.g. different material).
With control and programming via keypad or LECOM interfaces you tan Start the loading of a Parameter set under CO02. Under CO02 you tan also load the factory setting. Code CO02 Parameter (Factory setting is printed in bold) Name -OFactory setting Load Parameter set -lParameter set 1 -2Parameter set 2 -3Parameter Set 3 -4 Parameter set 4 Acceptance [SH + PRG] 5.2.
1 :ode ;116 Name Preselection: freely assignable digital output ;117 Function Cl16 ;118 Polarity for Cl17 for Parameter (Facto- setting is printed in bold) -lDigital output Al -2Digital output A2 -3Digital output A3 -4Digital output A4 -5 Relay output Kl l/K14 -oNo function -lOutput frequency smaller than Qmln -threshold -3Maximum current reached -4Ready -5 Pulse inhibit -6Fault indication -9Setpoint reached -lOAct. value = setpoint -1 lAct.
5.4.2 Maximum current reached, Imax When the output current has reached the maximum current limit which is programmed under C022, the red LED on the keypad is illuminated and the assigned output sends a message. In case of overload, the output frequency is automatically reduced (Vif reduction) to prevent a further rising of the motor current. You tan also use the maximum current limit, e.g. to accelerate the drive at the set maximum current limit.
The status of “pulse inhibit” is indicated by the illuminated yellow LED on the keypad and the permanently assigned digital output terminal 45. Pulse inhibit means that the output of the frequency controller is inhibited. Possible Causes are: l l l Controller inhibit Fault indication TRIP Under-/Overvoltage (see page 99) If you need the permanently assigned output terminal 45 with inverted polarity you must use a freely assignable output and set the polarity as required. 5.4.7 Act.
5.5 Monitor Outputs The controller has two monitor Outputs (terminals 62 and 63), to output internal Signals as voltage or current Signals. The required switch settings tan be obtained from the table on page 31 entnehmen. - Factory setting: output Functlon Relationship Terminal 62 Terminal 63 Output frequency Motor current 1 OV corresponds to 1 OV corresponds to fdmax Imaxunit If you need another Signal for an output, first select under Cl 10, which output you want to Change.
5.6 - Digital frequency output X9 (Option) The connection of drives via digital frequency allows a simple and precise control of multi-motor Systems. The digital frequency output X9 tan be used here as digital frequency encoder, e.g. for parallel or Slave drives.
6 Additional open-loop and closed-loop control functions 6.1 Chopper frequency The controllers of the 8600 series offer the feature to adapt the chopper frequency of the controller to the noise and smooth running requirements of the motor. By increasing the chopper frequency you tan generally reduce the motor noises which are generated by the pulsating output voltage. By reducing the chopper frequency the smooth running in the low frequency range is often improved.
6.1 .l Automatic chopper frequency reduction - If you want to operate the frequency controller with 4 kHz (Cl43 = -2- to -6-) or a higher chopper frequency, but also require an improved smooth running with low Speeds, you tan activate an automatic chopper frequency reduction, restricted to this range. For this, enter the output frequency under C143, below which the chopper frequency is to be reduced automatically to 2 kHz.
6.4 S-shaped ramp generator characteristic For the ramp generator of the main setpoint you tan select two different characteristics under Cl 34: l linear characteristic for all constant accelerations l S-shaped characteristic for all jerk-free accelerations. Parameter Code Name Cl34 R a m p - g e n e r . Q characteristic -l(main setpoint) 6.
-_ 7 Overload protections 7.1 Overload protection of the frequency controller (Lt monitoring) The frequency controllers have an output current monitoring to protect them against overload. You tan adapt this protection to the maximum ambient temperature to be expected. The lower the max. ambient temperature, the higher the limit of the permissible continuous output current. The permissible continuous output powes rises the same way.
C :ode lame CZl20 ‘unction 319 for Parameter (Factoty setting is printed in bold) ForC119=-0-.-l.oMonitoring not active -lMonitoring active, sets trip -2Monitoring active, sets warning ForC119=-1% Rated power for temperature range up -Clto 50°C -lIncreased power for temperature range up to 45°C -2Maximum power for temperature range up to 40°C 8 Display functions 8.1 Code set kceptancc :H + PRG All Codes in the controller are arranged in different code Sets.
8.2 Language Under code CO98 you tan select the language of the display texts. The Standard setting is German. Code CO98 Name Parameter (Factory setting is printed L a n g u a g e -OGerman -lEnglish -2- t 8.3 in bofd) Acceptance SH + PRG French Display of actual valuesAct. value Under Codes CO50 to CO54 you tan read different atiual values. Act. value Display Output frequency Act.
9 Dancer-Position control 9.1 Application examples 9.1.1 Winding drives l l Dancer-Position control with and without diameter Pilot control of centre winder - Winding and unwinding of different materials, e.g.
9.1.2 Line drives - l l Dancer-Position control with and without Pilot control of the line Speed Dancer-Position control with Speed adaptation and Pilot control of the line Speed VSdl -v T 86xx L 1 -166~~ VOOSl T Damm-controlled line drive 9.1.3 Grinding and cutting-off wheel drives l Control of contstant surface Speed via non-contact diameter detection. d d 1 Grinding or cutting-oft wheel drives Important information about the dancer-Position control: l l The analog inputs Xl /terminals.
9.2 Control structure of dancer-Position control with Pilot control for winding drives The following figure Shows the control structure of the dancerPosition control with Pilot control of the field frequency depending on the diameter (CO05 = -2Ol- or -202-). f-sei + f-correction Diameter or distance conlroller Vset Set Position Cl81 f-set = Diameter 8600 Vset (e.g. master voltage or digital frequency) Block diagram: Winding with diameter detection and dancer 9.2.
The controller divides the Speed setpoint by the actual winding diameter. The Speed setpoint tan either be provided by a JOG value, an analog input terminal X8, or by the digital frequency input X5. When changing the operating mode, also the operating unit or one of the LECOM interfaces are available. This procedure allows a Pilot synchronization of the circumferential Speed of the bale to the line Speed. That means that the field frequency is high for small diameters and low for large diameters. 9.2.
9.5 l Adjustment of analog inputs Offset adjustment of the analog input terminals 7/8 (setpoint input 1) and terminals 1/2 (setpoint input 2): - Adjustment only with activated controller inhibit (e.g. via low Signal at terminal 28). With the final configuration CO05 = -2Ol- or -202-, an unwanted Operation of the drive may occur during adjustment and activated controller enable.
- The following codes at-e important for the setting of the analog inputs: -- - :ode ;025 Iame Wselection: incoder :026 Zonstant ;025 :027 >046, for idjustment fot ;025 Parameter (Factory setting i s printed in bold) -lAnalog input Xl/terminals 1/2 .2Analog input Xllterminals 3/4 .
9.6 Selection of the configoration The setting of CO05 determines which input channels and which controls will be activated: ,, _,, /, > : ., _’ ‘1 j”. _, ,jj’ :,I I ,, :,,: I _‘_ .., 1Setpoint 1 = 1Setpoint 2 = 1line Speed 1 diameter d a n c e r Signal 1Terminals 718 (bipolar) or LECOM (bipolar) or .
Distance (a) Code Cl 80 *--Distance (a) plus radius (r) Exarnple current radius (r) = minimum radius current distance between ultrasonic Sensor and surface of winding bale (a ) Voltage supplied by the ultrasonic Sensor Cl880 = 150mm = 1000 mm := 8V = 9.2 V = 8 V ‘Ooo rom,o+;T mm 9.7,.2 Signal of the ultrasonic Sensor: radius Signal For setting the diameter detection by means of an ultrasonic Sensor which detects the diameter Signal, zero has to be programmed via code Cl 80. 9.7.
9.7.4 Gain adjustment - radius Signal When selecting the dancer-Position control with diameter evaluation of the setpoint, the gain of the radius Signal must be set such that an appropriate output frequency is generated when having a fixed setpoint and a certain radius. - Coarse adjustment: 1. Before adjusting the radius Signal, the analog inputs must be set. 2. Set CO25 = -l-. 3.
The following Codes are important for the adjustment of the radius detection: :ode :025 :027 lame Yeselection: .ncoder ,djustment :025 IParameter (Factory setting is printed in bold) I”“’ I-lAnalog input Xl/terminals 1/2 -2Analog inbut Xliterminals 3/4 -4Analog input Xllterminal 8 -lODigital frequency/incrementaI encoder input X5 -llDigital frequency/incrementaI encoder input X8 for CO25 = -l-, -2-, -4ON-LI NE (preselection of the analog inputs): 1 .ooo -2.500 (0.
9.8 Adjustment of the dancer-Position controller 9.8.1 Setpoint Provision - The act. value Signal of the dancer-Position controller is set via the terminals 3 and 4. The input Signal is displayed as percentage under code CO51 with Cl72 = -O-. In this case IOV = 100%. The input Signal is resolved with 12 bits (iOV/4096 = 2.44mV) plus sign. For the input of the dancer-Position setpoint, the dancer must be adjusted normally to the desired operating Position.
9.8.2 Winding or unwinding Winding from above or from below The command “unwinding from above” or “unwinding from below” is given by the CW/CCW reversal (reversing command e.g. via terminals 21 and 22). Unwinding from above or from below For unwinding, the sign for the influence of the dancer-Position Controller must be inverted. This achieved by the following: l Change the polarity of the voltage supply for the dancer Potentiometer. l Invert the act.
9.9.1 Overlay of Position controller The function “overlay of position controller” is necessary for the Start of the winding-up process with the dancer in an extreme Position. The full effect of the dancer-Position controller could lead to extreme operating conditions. Therefore the slow overlay of the output Signal is necessary when starting the winding-up process. The function “overlay of Position controller” tan be achieved via freely assignable terminals, keypad, or the serial interface.
9.9.2 Conversion of modulation of dancer-Position controller to field frequency Code Cl 91 is a calibration factor which is used to convert the modulation of the dancer-Position controller into a frequency. The unit of this code is mHz/%. That means that the user assigns the corresponding field frequency with 1% modulation of the dancerPosition controller. Example: With Cl 91 = 290 mHz/%, 100% modulation of the dancer-Position controller corresponds to a field frequency of 29 Hz.
To activate the diameter compensator the threshold which is to be set under C94 must be decreased so that the dancer-Position controller tan be activated. With the setting of Cl 94 = 100 % (factory setting) the diameter compensator is disconnected from the dancer-Position controller. - 9.10.1 Reset of the diameter compensator The diameter compensator tan be reset (e.g. after finishing the winding process) via a freely assignable digital input, the operating unit, or the LECOM interfaces.
1.0s 10s {lOO ms) 11 SI 1.0 s 10s 100 s (100 ms} 11 SI (10) Diameter compensator active Diameter compensator reset 10.0 s 100s 1.00 s ON-LINE 10.0 s 100s 990 s SH + PRG 9.10.2 Sensorless diameter detection -. The diameter compensator tan also be used for indirect diameter detection where there is no diameter detection System.
9.12 Application: Tandem winder 9.13.1 Digital frequency output The digital frequency output is required e.g. for a master Slave coupling (two motors are connected by friction to one winder shaft). For master-Slave couplings it is important that, in case of Speed reduction of the master, e.g. due to the current limiting function Imax,, the Slave Passes the same field frequency to the motor as the master. A frequency Signal which is proportional to the field frequency tan be supplied to terminal X9.
9.13 -_ Application: Loop control with Speed adaption Among others, a loop control is required for the transport of material by means of two conveyor belts. The slack which occurs between the two conveyor belts is kept constant by the loop control. To ac:tivate the loop control the code Cl 89 must be set to -0- but only with activated controller inhibit. Usually the field frequency Pilot control is not used for the loop control. Therefore e.g. 2V has to be entered under Cl80 as diameter setpoint.
9.14 Signal flow Chart for dancer-Position control (CO05 = -201- or -202-) Keypad.
Ramp gelwamr cup”t = -0. lS9 owl.q, multiplicalim mm Im,” sel.
10 Torque controller - 10.1 Features The torque control is used to supply a torque which is proportional to the setpoint, depending on a torque reference at a connected AC asynchronous machine. For this, the torque setpoint is entered via an analog Signal input which is permanently compared with the torque supplied to the motor shaft. If the torque setpoint exceeds the act. value torque, the field frequency and thus the output voltage is reduced until setpoint and act. value are identical. If the act.
- Block diagram Field frequency Conditions l l l The torque control tan only be used in the motor mode and in the armature setting range (range of constant motor excitation from 0 to V/f-rated frequency). In this configuration, only one motor tan be connected. The torque control has an Optimum effect only with activated magnetization current control (CO06 = -1-) . 10.
:ode :005 10.3 lame :onfiguration ‘arameter (Fectory sefting is printed in hold) OOpen-loop control, unipolar, lOpen-loop control, bipolar with additional setpoint 2Open-loop control with digital frequency a n d a d d i t i o n a l setpoint llClosed-loop c o n t r o l w i t h a n a l o g act. value 13Closed-loop c o n t r o l w i t h incremental encoder act. value 14Closed-loop control with digital frequency setpoint via X8 and Incremental encoder act.
Terminal 7 Switch Position use LevellResolution 1Remarks I 1internal ground (GND) 1 8 Master voltage or master current (depending On switch 5114) -lov to +lOV 12 bit + sign Code CO51 tan be used to display the torque setpoint of terminals 3 and 4. When Cl72 is set to -0-, CO51 is displayed as a percentage.
10.4 Adjustment of the Io setpoint that the Io current of the connected asynchronous machine is set according to the description under chapter 3.7.2 under code CO20. It is important Code Name Parameter (Factory setting is printed in bold) CO06 C o n t r o l m o d e -OV/f-characteristic control -lIo -control (only for Single drives) Io-setpoint CO20 Rated setpoint (PN,,,~,~~ = PNunit) 0.0 A as from 100 A (0.1 A} (1 Al - Acceptance [SH + PRG] ON-LINE 100.0 A INFO: Adjustable from 0.0 to 0.
The quality of the control behaviour is set via the Vp-gain factor CO77 and the adjustment time Tn C078. Therefore the field frequency is reduced with a reduction of the torque setpoint, until the ratio between Speed and torque is stable. If the ,torque setpoint is increased, the field frequency increases. Here, the field frequency input via terminal 8 or via the digital frequency input or via code CO46 is used to limit the maximum field frequency.
10.7 Signal flow Chart for torque control (CO05 = -2O- or -21-) P 250R 8 CO25 0326 offset Keypad, LECOM (nd for CO05 = -2.. -14., Cl 0 . ..ZOmA 4...ZOmA I fdmin Gain \ L --1. & -159 -0. - Analog set-value tipdar -20 Digital frequency hp9) -i ä _ Keypad. LECOM -7 Co05 Configuration Scaling Gain t” f dmax Scaling 10 fdmax -0. @qj free digital inputs Keypad, LECOM Iree dlgilal input 3ctm of rotabon digital Inputs Keypad, LECOM -0. O--W\ -0; -1...:15. 5 CO05 Ei...
Ramp generator for auick sh _ l cle Ramp generator output = ramp generator input l aJlPuts Deceleraficn ti ramp generatorwtfwf = ramp Qmerator input Keypad, LECOM 7tr#ij setting rang0 - Total Set-vaiue Standard Ti tlmes nr/-Efo 15 addit.
11 Code table The following table Shows which settings you tan enter under which Codes. For detailed explanations of the Codes and their possible functions refer to the corresponding chapters. How to read the Column Code Parameter Acceatance Zode 2000 2001 c CO02 CO03 CO04 130 code Abbreviation CO00 coo5* Q 1 (l} 9 9 INFO: Name ON-LINE SH + PRG [SH + PRG] table: Meanlng Code of the Standard code set Code of the extended code set Factory setting is printed in hold.
-Zode rlame Parameter (Factory setting is printed in hold) kceptano :005 Zonfiguration -o- SH + PRG -l-2-1 l-13.14- .15- .20- ,Zl- -. ,201- 202- :008 Output Signal digital frequency :009’ LECOM 1 unit address Open-loop control, unipolar, Open-loop control, bipolar with additional setpoint Open-loop control with digital frequency a n d a d d i t i o n a l setpoint Closed-loop control with analog act. value Closed-loop control with incremental encoder act.
6kHz variable 8kHz variable 12kHz v a r i a b l e 16kHz variable Rated setpoint (PNmotor = PNunit) as from 100 A quencylincremental (preselection of the analog inputs): xxxx mV factory setting CO25 = -lO-, -ll(preselection of the digital-frequency 1024 pulse/Hz or increments/revolution 2048 pulse/Hz or increments/revoiution value 132 encoder
Code Name Parameter (Factory setting is printed in hold) CO30’ C o n s t a n t f o r -l512 pulses/Hz or Incrementslrev. digital -21024 pulses/Hz or increments/rev. frequency -32048 pulses/Hz or increments/rev. loutput x9 l-44096 pulses/Hz or increments/rev. C O 3 4 M a s t e r current -OO...20mA -l4...20mA CO36 Voltage for 0% 0% IO.1 %} DC-injection brake Co38 Preselection: -lJOG 1 -2JOG 2 JOG frequency . .. -15JOG 15 C O 3 9 Setpoint CO38 for 50.
C ode C :054 Name Parameter (Factory setting is printed in bold) Motor current x.x A C :067 Fault indication C:068 Operating stiit0 cceptance INFO: Actual-value display xxx 48 INFO: Display of a faulffwaming l & b i t Status i n f o r m a t i o n 41 INFO: Only readable via LECOM 8-bit Status infomration 41 C:069 Controller state C:070 Gain of PI controller C:071 Adjustment time of PI controlller 0.10 s 0.01 s 1.0s 10s C:074 Influence of PI controller 0.0 % 0.0 % (O.Ol} IO.
- Code Name Cl00 Preselection: Additional acceleration / deceleration time Acceleration time for Cl 00 Cl01 Cl03 -15- 1 .OO s ON-LiNE 10.0 s 100s 9 9 0 SI 85 0.00 s 1.0 s 10s 100s ( 1 0 ms} 1100 ms) 11 4 110) 1 . 0 0 s]ON-LINE 10.0 s 100s 999 s 2.5 s c Ieceleration time for quick stop 5.0 s Cl 08 Gain for Cl 10 Cl11 85 Deceleration time for Cl00 999 s Holding time for DCinjection brake Cl10 1 .OO s ON-LINE 10.0 s 100s 990 s 0.00 s 1.0 s 10s 100s 0.00 s 1.
:ode N a m e :112 ;113 Parameter (Factory setting is printed in hold) Preselection: -1. digital input El -2digital input E2 freely ... a s s i g n a b l e _._ digital input -Eld i g i t a l i n p u t E8 No function Function for -OCl12 -lEnable additional acceleration and deceleration times Enable JOG frequencies -2-3- Reset trip -4- Set trip .
:ode N a m e -:119 Preselection: Monitoring :120Ifunction Cl19 :125* Baud rate :130 Enable additional ramp times :131 Ramp gener. stop Rampgenerator inpi = 0 Ramp-gener. characteristic :132 :134 ‘arameter Factory setting is printed in bold) & Digital input TRIP-Set lPTC input 15Output power (1 t monitoring) :orCllQ=-O-.
Code Name Cl80 Distance + radius Cl 81’ DancerPosition controller setpoint Cl82 DancerPosition controller Pcomponent Vp DancerCl83’ Position controller Icomponent Tn Cl 84’ DancerPosition controller reset 1-component C185’ DancerPosition / l ““r -+dnr I.IYIII. -ncomponent kd C186” +lO.OO V ON-LINE CLOOV -1 o.oov +lO.OO V ON-LINE 112 1 0.1 100 ON-LINE 112 9999 ms 20 ms (10 ms} I-component active -l- 1-component 0.0 9999 ms ON-LINE li3 SH+PRG 1 1 3 5.0 ON-LI NE 113 reset 0.
- Ll controller value lenze INFO: Process datum only readable via LECOM 139 l
12 Serial interfaces - The frequency controllers tan communicate with superimposed hosts (PLC and PC) and the Lenze operating units 323 and 324 via the serial interfaces LECOMl and LECOM2. 12.1 LECOMI interface X6 The LECOMl interface (X6 connector) tan be used to connect devices to the RS232C Standard (LECOM-A) or to the RS485 Standard (LECOM-B). The interface is suitable for Parameter setting, monitoring, diagnosis, and simple controls.
12.2 LECOM2 interface (Option) For more sophisticated applications, you tan use a field bus connecting interface. In the programming section, this interface is called LECOM2. For the bus System Interbus-S the connecting interfxe 2110 with the DRIVECOM Profile is available. For the bus System PROFIBUS the connecting module 2130 is also available with DRIVECOM Profile. The modules 2110 and 2130 are available are Options and tan be integrated into the controller (See also page 52). 12.
12.3.5 Baud rate (LECOMI) Under code Cl 25 you tan enter different baud rates. Code Cl25 Parameter Meaning 9600 baud 4 8 0 0 baud 2 4 0 0 baud 1200 baud 4% -l-2-3- 12.3.6 History of reset faults Under Cl 61 to Cl 68 you tan read the last eight faults stored. The last reset fault is displayed in Cl 61. 12.3.7 Code bank (LECOMI) With version 1 .O of the LECOM A/B protocol, Codes up to C255 tan be processed. To resch also higher numbers with this Version, the accessible range tan be changed by code C249.
12.3.9 High resolution data Under Codes C380 to C382 you tan enter very precise setpoint and act. value with a resolution of 14 bit plus sign. Setpoint 1: Setpoint scaled to the maximum frequency. The value of 214 corresponds to 100% of the maximum field frequency. The inforrnation is identical with that under C046, with the differente that you tan read the controller value directly thus excluding conversion errors.
12.4 Attribute table If you want to write programs yourself, the following table gives you information for the serial communication via LECOMl (LECOMNB) or LECOM2. Legend Zode Meaning Zode 3s Lenze code number Data structure E= S i n g l e v a r i a b l e (only o n e P a r a m e t e r e l e m e n t ) A= Array variable (several Parameter elements tan be selected by the code preselection or by LECOM sub Code).
Code DS SIP DT CO00 CO01 E E P - FIX32 FIX32 1 1 4 4 CO02 CO03 CO04 E E E P P P FIX32 FIX32 FIX32 4 4 4 1FIX?? . . . - - 1 1 1 II 1 FIX32 11 P P P P FIX32 FIX32 FIX32 1F I X 3 2 E E E E I DE DIL LCM-RM! LCMl Form. VD VD LCMZ Index 24575 24574 24573 - 24555 24554 24553 24550 24549 - 24546 24546 24545 IA I ’ Ra Ralw Ralw Ralw Ra I ..-..
Cl08 Cl09 [ Cl32 IE [Cl60 IE ]P IP 1Fix32 f FIX32 jP 1FIX32 [VD 1FIX32 IS 1FIX32 j1 , l-l*3L I ,r 1F I X 3 2 1 14 i FIX27 1 14 IC165 jE /Cl67 JE JP } FIX32 Cl68 Cl72 Cl76 JE JE jE JP 1F I X 3 2 c210 c211 C212 IG213 1na ]Fia ,.
147
Service 1 Fault indication When a fault occurs, the Operation of the frequency controller is immediately interrupted and the Signal “ready” is removed. The fault is displayed automatically under C067. The fault indication is flashing as long as the fault has not been reset. Fault reset: Press SH + PRG or activate the input TRIP reset. Reset fault indications are stored. They tan be displayed again by selected code CO67 and pressing the DOWN-key in the Parameter level.
List of fault indications Display on ceypad .__ Display on host 3 11 3Cl :ault IO fault ;hort circuit/ Earth fault :ontroller Iverload 3c5 -Aotor overload X6 Iverheat leatsink Cause Remedy Short circuit/earth fault at the motor side e.g. by - defective motor cable - contact of motor windings - contact between motor housing and winding Frequent o r t o o l o n g accelerations with overcurrent Permanent overload with motor current > 110% rafed current.
2 Warning A warning is displayed automatically under C067. During a warning the Signal “ready” is removed, however, the Operation of the frequency controller is not interrupted. Press SH + PRG or activate the input TRIP met.
4 Checking the power Stage The measurements described below are to be carried out only by skilled specialists. Use a digital Voltmeter. The measuring values indicate the nominal value. If they are different, there is a defective. 4.1 Checking the mains rectifier Disconnect controller from the mains and wait until the DC bus has discharged (approx. 3 minutes). You tan measure directly at the power terminals. ?ii%E Diodes in reverse 4.2 -UG -+ L2 -UG+ L 3 +UG -i Ll Measuring value = 0.4v - 0.4v = 0.
Index A Acceleration time 74 Addjtional 86 Additional, Enabling with control via keypad or LECOM 87 Additional,Programming 86 Additional. Enabling with terminal control 87 Additional 86 Accessories Brake resistors 38 Mains Chokes 42 Motorfilter 45 RFI filters 50 Sine filter 47 Act. vatue 124 analog 75 digital 75 Act. value = setpoint 93 Act. value display 80 Act.
D Deceleration time 74 Additionaj, Enabling with control via keypad or LECOM 87 Additional, Ti inputs 86 Additional, enabling with terminal control 87 Additional.
L LECOMZ 141 LECOM-A/B 53; 140 Level converter 2101 IP 53 LECOMA/B Level converter 2101 IP 140 LECOM-LI 53 Load-Change damping 98 M Magnetizing-current control (IO control) 70 Main setpoint Ramp generator 74 Mains Chokes 42 Advantages 42 Mains voltage 11 Mechanical installation 22 Minimum output frequency (minimum field frequency ) 73 Monitor Signals 80 Monitoring 150 Motor temperature 31 Motor drifting 80 Motorfilter 45 Advantages 45 Motor overload 149 Motor protection 24; 99 N Networking 52 DRIVECOM Pro
Q Quick stop 60 R Ramp generator Input = 0 (RFG/E=O) 88 Input = 0, Keypad or LECOM 88 Input = 0, Terminal control 88 Sshaped characteristic 98 Stop, keypad or LECOM 88 Stop, Terminal control 88 Ramip generator stop stop 88 Ready (RDY) 92 Relative humidity 11 Reset Warning 150 Fault 148 RFI filters 50 S Scre(enings 37 Select direction of rotation 61 Selection controller 19 Setpoint 1 Features 66 Input 31 with control via keypad or LECOM 66 with terminal control 66 Setpoint 2 106; 124 Features 68 Input 31 R
Lenze GmbH & Co KG, Postfach 1013 52, D-31763 Hameln, Geschäftsfeld Elektronik, Standort: Groß Berkel, Hans-Lenze-Straße 1, D-31855 Aerzen, Telefon (051 54) 82-0, Telefax (051 54) 82-21 11 E-Mail: LenzeQLenze.de . Internet: http://www.Lenze.