4.2.3 CE-typical drive
System
Components of the CE-typical drive
sytem
Controller,
RFI
filter and mains
Choke
are mounted on one
assembly board.
The
System
components are
functionally
wired according to the
chapter
5, section: Planning of the Operating Instructions.
Installation of CE-typical drive Systems
The
electromagnetic
compatibility of a
machine
depends on the
method and accuracy of the
installation.
Special
care
must be
taken of:
l filters,
l
screens
and
l grounding.
Filters
Only use suitable mains filters and mains Chokes.
Mains filters reduce impermissible high-frequency disturbances to a
perrnissible value.
Mains
Chokes
reduce low-frequency disturbances, especially those
caused
by long motor cables.
Motor cables
which
are longer than 50 m must be protected
additionally (motor filter or sine filter).
Screens
All cables from and
to
t3e
controller
must be screened.
Lenze
System
cables meet these requirements.
Ensure that the motor
cable
is laid separately from the other cables
(Signal
cables and mains cables). Mains input and motor output
must not be connected
to
one terminal
Strip.
Lay cables as
close
as possible to the reference potential. Dangling
cables are like antennas.
Grounding
Ground
all metall-conductive components
(controllers,
mains filters,
mains Chokes) using suitable cables from a
central
Point
(PE bar).
Maintain the min.
Cross
sections
prescribed in the safety
regulations. For EMC, the
surface
of the contact is important, not
the
Cross
section.