Appendix
Index table
10
122
KHB 13.0003-EN 2.0
Characteristics
Possible settingsNameIndex
DescriptionSelectionLenze
1011
h
Restore_default_
parameters
1 restore_all_default
_parameters
00000001
h
00000000
h
{1
h
} 64616F6C
h
VAR UINT3
2
RW —
Loading the default
parameter set, only
possible when the power
stage is deactivated.
The CAN communication
parameters (node No.,
baud rate and operating
mode) remain unchanged.
64616F6C
h
Load Loading the default
parameter set.
00000001
h
Read access: Reset to
default values.
1014
h
0 COB-ID_emergency
_message
00000081
h
00000000
h
{1
h
} 00000081
h
VAR UINT3
2
RW —
Identifier emergency
object,
080
h
+ node address
Bit No. Value
0-10 X 11-bit identifier
11 - 28 0
The extended identifier
(bit 29) is not supported.
Every bit in this range
must be set to ”0”.
29 0
30 0 Reserved
31
0 Emergency object exists /
is used
1 Emergency object does not
exist / is not used
1015
h
0 inhibit_time_emcy 0
0 {1 μs} 65535
VAR UINT1
6
RW —
Setting the inhibit time of
the emergency object. The
time must be a multiple of
100 μs.