Manual
Single-axis controllers
Wiring
Devices in the range 32 ... 104 A (15 ... 55 kW)
4
120
EDS94SPP101 EN 7.1
Motor temperature monitoring
Terminal X106 Labelling Description
T1
T2
Motor temperature monitoring with PTC element (type-A sensor,
switching performance according to EN 60947-8 for type-A tripping units)
or thermostat (NC contact).
SSP94X6106
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
2.5
12 0.5 ... 0.6 4.5 ... 6.2
Slot
0.6 x 3.5
With wire end ferrule
Motor brake control (optional)
Note!
When the 24 V supply voltages (at X2) are applied and a motor holding brake
is available, the devices respond as follows:
ƒ SingleDrive without mains or DC-bus voltage: The motor holding brake
cannot be released.
ƒ MultiDrive without DC-bus voltage: The motor holding brake can be
released.
Terminal X107 Labelling Description
Connection of the motor holding brake
BD1
BD2
+(Lenze:WH)
-(Lenze:BN)
E94AZHx0101: 24 V DC, max. 5.0 A
Observe correct polarity!
+/-
Supply voltage for the motor holding brake (18 ... 30 V DC)
Observe correct polarity!
SSP94X6107
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
2.5
12 0.5 ... 0.6 4.5 ... 6.2
Slot
0.6 x 3.5
With wire end ferrule
Stripping length or contact length: 8 mm
Tip!
For detailed information on the motor holding brake control modules, please
see the chapter Accessories ( 419).