Manual

Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
121
EDS94SPP101 EN 7.1
4.6.6 Devices in the range 145 ... 695 A (75 ... 370 kW)
Device size 8S
SSP94KL08S
Fig. 4-26 Arrangement of the power connections
Tip!
The barrier between mains input and power terminals can be dismounted to
have more free space for wiring.
Motor
Terminal X105 Marking Description
U
V
W
Motor phases
SSP94KL0X8
Connection for the PE conductor on the motor side with M8 ring
cable lug
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Device size 8S:
Flexible
With wire end ferrule
95
000 14 124 Inbus 5
M8 ring cable lug 95 000 9.5 84 WAF 13