Manual

Single-axis controllers
Wiring
Devices in the range 145 ... 695 A (75 ... 370 kW)
4
123
EDS94SPP101 EN 7.1
Operation with DC supply
Foroperation with DC supply, the internal fans must be connected via the internal terminal
FK103 to the 400/500 V AC mains voltage.
When opening the upper housing cover, you will find the pluggable terminal FK103 at the
top in the device on the s witched-mode power supply card.
94SSPGG852
Interface card
Switched-mode power supply card
FK103 Fan voltage terminal
Remove the cable bridges of the terminal. Then, connect the mains voltage to
FK103.101/100.
FK103 Labelling Description
101
103
NC NC
100102
101 Fan L1
by default bridged
103 Mains phase
(internal)
NC
not assigned
NC
100 Fan L2
by default bridged
SSP94FK103
102 Mains phase
(internal)
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
2.5
12 0.5 ... 0.6 4.5 ... 6.2
Slot
0.6 x 3.5
With wire end
ferrule
Rated values - internal fan, AC 400 V
Gg Type I[A] P[W]
8S E94ASxE1454 0.3 120
8 E94ASxE1724
E94ASxE2024
1.2 480
9 E94ASxE2454
E94ASxE2924
E94ASxE3664
1.2 480
10
E94ASxE4604 1.2 480
E94ASxE5724
E94ASxE6354
E94ASxE6954
2.8 1120