Manual

Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 230 V
6
219
EDS94SPP101 EN 7.1
6.3.1 Operation at rated mains voltage 230 V
Basis of the data
Mains Voltage Voltage range Frequency range
U
LN
[V] U
LN
[V] f[Hz]
3/PE AC 230 180-0%...264+0% 45-0%...65+0%
Input data
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C c max. +55 °C c
E94APNE0104 230 50/60 8 6 3
E94APNE0364 230 50/60 29 21.8 3
E94APNE1004 230 50/60 82 61 3
E94APNE2454 230 50/60 200 150 3
c Temperature in the control cabinet
Voltage Continuous input power
Type [V] S
L
[kVA]
E94APNE0104 230 3.2
E94APNE0364 230 11.5
E94APNE1004 230 32.6
E94APNE2454 230 79.6
Output data
Basis of the data
Mains Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f[Hz]
2/PE DC 325 260-0%...370+0% -
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C c max. +55 °C c
E94APNE0104 325 0(DC) 10 7.5 2
E94APNE0364 325 0(DC) 36 27 2
E94APNE1004 325 0(DC) 100 75 2
E94APNE2454 325 0(DC) 245 184 2
c Temperature in the control cabinet