Manual
Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 230 V
6
220
EDS94SPP101 EN 7.1
Output current and output power
100 % 5-s cycle 3-min cycle
Type I
DC
[A] P
DC
[kW] I
DC
[A] P
DC
[kW] I
DC
[A] P
DC
[kW]
E94APNE0104 10 2.1 40 8.4 15 3.2
E94APNE0104
+ E94AZMP0084
10 2.8 40 11.2 15 4.2
E94APNE0364 36 7.5 108 22.5 54 11.3
E94APNE0364
+ E94AZMP0294
36 10.1 108 30.3 54 15.5
E94APNE1004 100 20.8 200 62.4 150 31.2
E94APNE1004
+ E94AZMP0824
100 27.9 200 83.7 150 41.9
E94APNE2454 245 51 368 153 368 76.5
E94APNE2454
+ E94AZMP2004
245 68.5 368 206 368 103
100 % Permanent rated values
5-scycle Cycleforthesecond-range
(0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value)
3-min cycle Cycle for the minute-range
(60 s overload/120 s recovery time with 75 % of the permanent rated value)
Internal brake c hopper data
R
Bmin
[Ω]
I
BRmax
[A]
P
BRmax
[kW]
I
BRd
[A]
P
Bd
[kW]
t
Z
[s]
t
on
[s]
t
fp
[s]
Type
E94APNE0104 18.0
21.7 8.5 7.9 1.1 4.3 0.5 0.5
E94APNE0364 6.0 65.0 25.4 29.1 5.1 3.0 0.5 0.5
E94APNE1004 2.5 156 60.8 62.7 9.8 3.6 0.5 0.5
E94APNE2454 1.4 279 109 112 17.5 3.6 0.5 0.5
R
Bmin
Minimum brake resistance, nominal value ±10 %
I
BRmax
Peak current
P
BRmax
Peak braking power
I
BRd
Continuous current RMS - important for the dimensioning of the cables
P
Bd
Continuous braking power
t
Z
Cycle time, periodic load change with running time and recovery time
t
on
Running time
t
Z
-t
on
Recovery time
t
fp
Maximum running time without initial load and compliance with the recovery
time