Manual

Power supply modules
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
6
222
EDS94SPP101 EN 7.1
Output current and output power
100 % 5-s cycle 3-min cycle
Type I
DC
[A] P
DC
[kW] I
DC
[A] P
DC
[kW] I
DC
[A] P
DC
[kW]
E94APNE0104 10 3.6 40 14.4 15 5.4
E94APNE0104
+ E94AZMP0084
10 4.9 40 19.6 15 7.4
E94APNE0364 36 13.0 108 39.0 54 19.5
E94APNE0364
+ E94AZMP0294
36 17.5 108 52.5 54 26.3
E94APNE1004 100 36.2 200 109 150 54.3
E94APNE1004
+ E94AZMP0824
100 48.6 200 146 150 72.9
E94APNE2454 245 88.6 368 266 368 133
E94APNE2454
+ E94AZMP2004
245 119 368 357 368 179
100 % Permanent rated values
5-scycle Cycleforthesecond-range
(0.5 s overload/4.5 s recovery time with 75 % of the permanent rated value)
3-min cycle Cycle for the minute-range
(60 s overload/120 s recovery time with 75 % of the permanent rated value)
Internal brake c hopper data
R
Bmin
[Ω]
I
BRmax
[A]
P
BRmax
[kW]
I
BRd
[A]
P
Bd
[kW]
t
Z
[s]
t
on
[s]
t
fp
[s]
Type
E94APNE0104 27.0
26.9 19.5 9.7 2.6 4.3 0.5 0.5
E94APNE0364 12.0 60.4 43.8 27.0 8.7 3.0 0.5 0.5
E94APNE1004 5.0 145 105 58.2 17.0 3.6 0.5 0.5
E94APNE2454 2.8 259 188 104 30.3 3.6 0.5 0.5
R
Bmin
Minimum brake resistance, nominal value ±10 %
I
BRmax
Peak current
P
BRmax
Peak braking power
I
BRd
Continuous current RMS - important for the dimensioning of the cables
P
Bd
Continuous braking power
t
Z
Cycle time, periodic load change with running time and recovery time
t
on
Running time
t
Z
-t
on
Recovery time
t
fp
Maximum running time without initial load and compliance with the recovery
time