Manual

Power supply modules
Wiring
Design of the cables
6
244
EDS94SPP101 EN 7.1
6.6.3 Design of the cables
ƒ The cables used must comply with the approvals required for the location (e.g. UL).
ƒ It is imperative to comply with the regulations concerning minimum cross-sections
of PE conductors. The cross-section of the PE conductor must be at least as large as
the cross-section of the power connections.
ƒ The effectiveness of a shielded cable is reached by:
Providing a good shield connection through large-surface shield c ontact.
Using only braided shields with low shield resistance made of tin-plated or
nickel-plated copper braid.
Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
ƒ External brake resistor ( Mounting Instructions of the brake resistor)
The following connections need not be shielded:
ƒ Mains