Regenerative power supply modules
Mechanical installation
Mounting steps
7
290
EDS94SPP101-7.1
7.5.4 Mounting steps
Proceed as follows for the installation:
1. Prepare M5 threaded holes on the mounting plate according to the mounting grid.
2. Screw the installation backplane onto the mounting plate. Do not yet tighten the
screws.
Use M5 screw and washer assemblies or M5 hexagon socket screws with washers.
The screw joint in the installation backplane may not jut out more than 7 mm.
3. Repeat step 2 for other i nstallation backplanes, which can be mounted directly
adjacent to one another.
4. Align all installation backplanes.
5. If busbars are used: connect the busbars.
6. Tightly screw all installation backplanes onto the mounting plate.
Tightening torque: 3.4 Nm (30 lb-in).
Tip!
Before plugging the standard device into the installation backplane, read the
chapters ”Disconnect internal PE connection” ( 294) and ”Connecting
busbars” ( 296).