Manual

Regenerative power supply modules
Wiring
Earthing of internal EMC filters
7
295
EDS94SPP101-7.1
Implementing the measures
Proceed as follows to disconnect the internal connection between the filters and PE:
1. Remove IT insulating cap from the parking position c in the installation backplane.
For this apply a screwdriver on the right or left and lever off the insulating cap.
Optionally the insulating cap can be carefully removed using an appropriate pliers.
2. Attach IT insulating cap to the earthing jumper d until it clicks into place.
1
2
SSP94IT001
Fig. 7-8 Plugging the IT insulating cap onto the earthing jumper