Manual
Regenerative power supply modules
Wiring
Terminal assignment
7
299
EDS94SPP101-7.1
Mains
Terminal X320 Labelling Description
L1
L2
L3
Connection of t he L1, L2, L3 mains phases
Connection for the supply-side PE conductor w ith M5 ring cable lug
SSP94NF406
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
E94AZMR0264xDB 10 6 1.2 ... 1.5 10.6 ... 13.3 1.0 x 4.0
E94AZMR0474xDB 25 2 2.5 22.1 1.0 x 6.5
PE connection data
∅ Starting torque
[mm] [Nm] [lb-in]
E94AZMR0264xDB
M5
3 26.5 PH2
E94AZMR0474xDB
Terminal X111
(left part)
Labelling Description
L1
L2
L3
Connection of the mains phases
E94APNE0xx4/E94AZxPxxx4: L1, L2, L3
E94ARNE0xx4/E94AZMR0xx4xDB: L1.1, L2.1, L3.1
Terminal for the supply-side PE conductor with M5 ring cable lug
SSP940X111
Terminal X112
(right part)
Labelling Description
L1
L2
L3
Connection of the mains phases
E94APNE0xx4/E94AZxPxxx4:
alternatively at the bottom L1, L2, L3
E94ARNE0xx4/E94AZMR0xx4xDB: L1.2, L2.2, L3.2
Terminal for the supply-side PE conductor with M5 ring cable lug
SSP940X112
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Device size 3:
Flexible
With wire end ferrule
10 6 1.2 ... 1.5 10.6 ... 13.3 PH1