Regenerative power supply modules
Wiring
Wiring of control connections
7
300
EDS94SPP101-7.1
DC bus
Terminal X111
(right part)
Labelling Description
+UG
-UG
Alternative option for DC-bus voltage connection (compatible to
9300 series)
E94ARNE0244: maximum current I
dc
=50A
SSP940X111
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Device size 3:
Flexible
With wire end ferrule
10 6 1.2 ... 1.5 10.6 ... 13.3 PH1
External brake resistor
Terminal data
Max. conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Device size 3:
Flexible
With wire end ferrule
10 6 1.2 ... 1.5 10.6 ... 13.3 PH1
7.6.8 Wiring of c ontrol connections
Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Switch off the power supply and wait for at least three minutes before
working on the power terminals.
ƒ Make sure that all power terminals are deenergised.
Stop!
The device contains components that c an be destroyed by electrostatic
discharge!
Before working on the device, the personnel must ensure that they are free of
electrostatic charge by using appropriate measures.