Regenerative power supply modules
Wiring
Wiring of control connections
7
301
EDS94SPP101-7.1
Tip!
Parameter setting and configuration can be carried out using the
L-force »Engineer«. For this purpose the Online Help and the Software Manual
for the standard device will guide you.
System bus CAN on board
Terminal X1 Labelling Description
Pin 2 CAN-LOW
Pin 3 CAN-GND
Pin 7 CAN-HIGH
9400SSP000X1
(Housing) CAN-Shield
24 V supply
Terminal X323 Labelling Description
GE GND external supply
SSP9400X11
24E 24 V external supply through safely separated power supply unit
(SELV/PELV)
IEC 61131-2, 22.8 ... 28.8 V, residual ripple max. ±5 %
Current during operation: 450 mA
Starting current: max. 4 A f or 100 ms
Terminal data
Conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
0.2 ... 2.5
24 ... 12 Spring terminal
With wire end
ferrule
Stripping length / contact length: 10 mm
Terminal X2 Labelling Description
GE GND external supply
24E 24 V external supply via a safely separated power supply unit
(SELV/PELV)
9400SSP000X2
SB State bus in/out (reference GE)
Terminal data
Conductor cross-section Tightening torque
[mm
2
] [AWG] [Nm] [lb-in]
Flexible
0.2 ... 2.5
24 ... 12 Spring terminal
With wire end
ferrule