Manual

Accessories (overview)
Communication modules
DeviceNet
9
375
EDS94SPP101 EN 7.1
Terminal data
E94YCDN001C
The bus of the communication module is connected via the 5-pole plug connector with
double screw connection (X225).
Designation Cable colour Description
V+ red External voltage supply
z U=24VDC
z I
max
= 170 mA
CAN_H white Data line / input for bus terminating resistor (120 Ω)
SHIELD Shielding
CAN_L blue Data line / input for bus terminating resistor (120 Ω)
V- black Reference potential for external voltage supply
Type Values
Electrical connection Plug connector with double screw connection
Possible connections
rigid:
2.5 mm
2
(AWG 14)
flexible:
without wire end ferrule
2.5 mm
2
(AWG 14)
with wire end ferrule, without plastic sleeve
2.5 mm
2
(AWG 14)
with wire end ferrule, with plastic sleeve
2.5 mm
2
(AWG 14)
Starting torque 0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in)
Stripping length 7mm
External voltage supply
Note!
The communication module must be supplied externally via the DeviceNet
cable!