Manual

Accessories (overview)
Communication modules
PROFIBUS
9
377
EDS94SPP101 EN 7.1
Scope of supply
E94YCPM001A
Connections
Pos. Description
X200 External supply of the communication module
Design: Plug connector with screw connection, 2-pole
X201 Connection for PROFIBUS
Design: Sub-D socket, 9-pole
Displays
LED
Description
Pos. Co lour Condition
MS Green
On Communication module is supplied with voltage and connected to the
standard device.
Blinking Communication module is suppliedwith voltage, buthas no connectionto
the standard device (standard device is switched off, initialising or n ot
present).
ME Red On An error has occurred on the communication module.
BS Green Blinking Communication via the communication module has been established.
The PROFIBUS is active.
BE Red On Bus monitoring has been triggered.
DE Red On The communication module is not accepted by the standard device.
z See notes given in the instructions for the standard device.