Wiring of the PROFIBUS
Observe the notes and wiring regulations given in the documentation for the
control system.
ƒ Install a bus terminating resistor only at the first and last physical bus station.
The bus terminating resistor is integrated into the bus connector and can be
activated via a switch.
The bus terminator is fed by the bus station. When the communication module is
provided with an external power supply, ( 379) the bus terminator can be fed
independently from the power supply of the standard device.
ƒ Check/activate the bus terminating resistors.
ƒ Use the bus connector to connect the PROFIBUS with the controller.
ƒ Only use cables which correspond to the listed specifications ( 381).
Note!
ƒ The bus terminator must always be supplied. Otherwise, the bus can get
unstable.
ƒ If you want to disconnect individual bus stations, ensure that the bus
terminators at the first and last physical bus station remain active.
ƒ The bus terminator is no longer active if
the connector has been pulled out e.g. in the event of service.
the module supply has been switched off.
For further notes on the PROFIBUS network, please refer to the PROFIBUS
Communication Manual.