4.3 Rated data (devices for 400/500V mains)
The E94ASxExxx4 devices can be used in the voltage range of 180 V ... 550 V AC.
Note!
To ensure a faultless operation of the devices the code C00173 must be set
according to the mains voltage connected.
Emergency operation
Operation of the E94ASxxxx4 devices with an emergency voltage supply at +UG, -UG, is
possible from U
DC
≥ 260 V. The settings in C00173 and C00174 are to be adapted
accordingly.
Operation of the E94AMxxxx4 devices with an emergency voltage supply at +UG, -UG, is
possible with U
DC
≤ 260 V. The settings in C00173 and C00174 are to be adapted
accordingly. A 24-V supply at X2 is required.
4.3.1 Overview
Input data
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C c max. +55 °C c
E94ASxE0024 230/400/500 50/60 2.1/2.1/1.8 1.6/1.6/1.4 3
E94ASxE0034 230/400/500 50/60 3.5/3.5/3.1 2.6/2.6/2.3 3
E94ASxE0044 230/400/500 50/60 5.5/5.5/4.8 4.1/4.1/3.6 3
E94ASxE0074 230/400/500 50/60 9.9/9.9/8.6 7.4/7.4/6.5 3
E94ASxE0134 230/400/500 50/60 16.8/16.8/14.7 12.6/12.6/11.0 3
E94ASxE0174 230/400/500 50/60 21.0/21.0/18.3 15.8/15.8/13.8 3
E94ASxE0244 230/400/500 50/60 29.0/29.0/25.4 21.8/21.8/19.1 3
E94ASxE0324 230/400/500 50/60 29.0/29.0/26.0 22.0/22.0/20.0 3
E94ASxE0474 230/400/500 50/60 43.0/43.0/39.0 32.0/32.0/29.0 3
E94ASxE0594 230/400/500 50/60 54.0/54.0/47.0 40.5/40.5/35.3 3
E94ASxE0864 230/400/500 50/60 79.0/79.0/70.0 59.0/59.0/52.0 3
E94ASxE1044 230/400/500 50/60 95.0/95.0/84.0 71.0/71.0/63.0 3
E94ASxE1454 400/500 50/60 140/140 126/126 3
E94ASxE1724 400/500 50/60 166/166 149/149 3
E94ASxE2024 400/500 50/60 195/195 176/176 3
E94ASxE2454 400/500 50/60 237/237 213/213 3
E94ASxE2924 400/500 50/60 280/280 252/252 3
E94ASxE3664 400/500 50/60 354/354 319/319 3
E94ASxE4604 400/500 50/60 444/444 400/400 3
E94ASxE5724 400/500 50/60 553/553 498/498 3
E94ASxE6354 400/500 50/60 614/614 553/553 3
E94ASxE6954 400/500 50/60 672/672 605/605 3
c Temperature in the control cabinet