Manual

Accessories (overview)
Components for operation in the DC-bus connection
DC-feeding point
9
482
EDS94SPP101 EN 7.1
DC input module components
Pos. Description
Nameplate
X109 +UG busbar input
X110 -UG busbar input
X119 +UG cable input
X120 -UG cable input
X129 +UG cable output
X130 -UG cable output
Standards
Conformity and approval
Conformity
CE
2006/95/EC Low-voltage directive
Approval
UL UL 508C Power Conversion Equipment, File No. 132659
GOST-R 51321.1-2000
51321.3-99
No. POCC DE.AN30.B08815
Protection
Enclosure
EN 60529
IP 20
NEMA 250 Protection against accidental contact acc. to type 1
Insulation resistance EN 61800-5-1 Overvoltage category III
Reduction from 2000 m: Overvoltage category II
Operating conditions
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C:
Device size 1 ... 7: 2.5 %/°C
Device size 8S ... 10: 1 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800-5-1 Degree of pollution 2
Vibration resistance (9.81 m/s
2
=1g)
Transport
IEC/EN 60721-3-2 2M2
EN 61800-2
2...9Hz:amplitude3.5mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5...13.2Hz:amplitud1mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g