Manual
Accessories (overview)
Components for operation in the DC-bus connection
DC-feeding point
9
483
EDS94SPP101 EN 7.1
Rated data
Basis of the data
Mains Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f[Hz]
2/PE DC 325 260-0%...370+0% -
2/PE DC 565 455-0%...620+0% -
2/PE DC 705 565-0%...775+0% -
Voltage Frequency Current [A]
Number of
phases
[V] [Hz] max. +45 °C c max. +55 °C c
E94AZEX100 325/565/705 0(DC) 100/100/100 75/75/75 2
c Temperature in the control cabinet
Safety instructions
Danger!
Hazardous electrical voltage
During operation and up to 3 minutes after power-off, hazardous electrical
voltages may occur at the DC input module connections.
Possible consequences:
ƒ Death or serious injuries when touching the connections.
Protective measures:
ƒ Disconnect all devices in the DC-bus connection from the mains before
working on the input module.
ƒ Check if no voltage is applied to the power terminals.
Warnings!
ƒ Maximum surrounding air temperature: 55 °C
ƒ Use 60/70 °C copper wires only.
ƒ Use appropriate listed (ZMVV) wire connectors and soldering lugs, suitable
for current and voltage.
Note!
The place of installation and mounting material must ensure a permanent
mechanical connection.
We recommend to keep to the hole patterns of the axis modules when fixing
the DC input module. The hole spacing corresponds to device size I. For further
information, please see the Mounting Instructions for the axis module
installation backplane (EDK94ZPM113).