General data
Conformity and approval
Approval
UR UL508 Industrial Control Equipment, Underwriter Laboratories
(File-No. E219022) for USA and Canada
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
Other mains types Observe instructions for special measures in the
documentation for the basic device!
Protection of persons and equipment
Enclosure
EN 60529
IP20
Not in the wire range of the
terminals
NEMA 250 Protection against contact
to type 1
Earth leakage current IEC/EN 61800-5-1 >3.5mA Observe stipulations and safety
instructions!
Insulation resistance IEC/EN 61800-5-1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800-5-1 Pollution degree 2
Vibration resistance (9.81 m/s
2
=1g)
Transport
IEC/EN 60721-3-2 2M2
EN 61800-2
2...9Hz:amplitude3.5mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5...13.2Hz:amplitude±1mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertical
Free spaces
Dimensions
Weights