Manual
Accessories (overview)
Filters
Mains filters for regenerative power supply modules
9
513
EDS94SPP101 EN 7.1
General data
Mains data
Mains types
With grounded neutral (TT/TN systems)
Operation permitted without restrictions
IT systems Request specific m easures from Lenze
Protection of persons and equipment
Enclosure
EN 60529
IP20
Not in the wire range of the
terminals
NEMA 250 Protection against contact
to type 1
Earth leakage current IEC/EN 61800-5-1 >3.5mA Observe stipulations and safety
instructions!
Insulation resistance IEC/EN 61800-5-1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Current derating at +45 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: current derating of 5 %/1000 m
Pollution EN 61800-5-1 Pollution degree 2
Vibration resistance (9.81 m/s
2
=1g)
Transport
IEC/EN 60721-3-2 2M2
EN 61800-2
2...9Hz:amplitude3.5mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5...13.2Hz:amplitude±1mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 1 g
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertically
Free space The required free space results from the mounting position
and the specifications of the standard device.