Manual

Single-axis controllers
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
4
54
EDS94SPP101 EN 7.1
Device size 8S ... 10
Basis of the data
Mains Voltage Voltage range Frequency range
U
LN
[V] U
LN
[V] f[Hz]
3/PE AC 400 340-0%...440+0% 48-0%...65+0%
Mains current at I
aN
Output power Motor power
(typical)
with external
mains choke
without external
mains choke
U, V, W 4pol.ASM
Type I
LN
[A] I
LN
[A] S
aN
[kVA] P
aN
[kW] P
aN
[hp]
E94ASxE1454 - 140 90 75 100
E94ASxE1724 - 166 107 90 125
E94ASxE2024 - 195 126 105 140
E94ASxE2454 - 237 153 130 170
E94ASxE2924 - 280 182 150 205
E94ASxE3664 - 354 228 190 255
E94ASxE4604 - 444 287 240 320
E94ASxE5724 - 553 357 300 400
E94ASxE6354 - 614 396 335 445
E94ASxE6954 - 672 433 370 495