Manual

Accessories (overview)
Filters
Sinusoidal filter 180 ... 480 A
9
553
EDS94SPP101 EN 7.1
General data
Conformity and approval
Conformity
CE 2006/95/EC Low-Voltage Directive
Protection of persons and equipment
Degree of protection EN 60529
IP00
Earth leakage current IEC/EN 61800-5-1 >3.5mA Observe stipulations and safety
instructions!
Insulation resistance IEC/EN 61800-5-1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1 1K3 (-25 ... +60 °C)
Transport IEC/EN 60721-3-2 2K3 (-25 ... +70 °C)
Operation IEC/EN 60721-3-3 3K3 (-10 ... +55 °C)
Current derating at +40 ... +55 °C: 2.5 %/°C
Site altitude 0 ... 4000 m amsl
1000 ... 4000 m amsl: Current derating 5 %/1000 m
Pollution EN 61800-5-1 Degree of pollution 2
Vibration resistance (9.81 m/s
2
=1g)
Transport
IEC/EN 60721-3-2 2M2
EN 61800-2
2...9Hz:Amplitude3.5mm
10 ... 200 Hz: Acceleration resistant up to 10 m/s
2
200 ... 500 Hz: Acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd 5...13.2Hz:Amplitud1mm
13.2 ... 100 Hz: Acceleration resistant up to 0.7 g
IEC/EN 60068-2-6
10 ... 57 Hz: Amplitude 0.075 mm
57 ... 150 Hz: Acceleration resistant up to 10 m/s
2
Mounting conditions
Mounting place
In the control cabinet
Mounting position Vertical, fixing bracket below
Free space 100 mm to the side and above