Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
4
57
EDS94SPP101 EN 7.1
For the selection ”Mode 1“:
Output currents [A] at switching frequency
2kHz
Type I
aN2
I
aNhc
I
aMhc
I
aMre
E94ASxE1454 145 160 218 145
E94ASxE1724 172 195 258 180
E94ASxE2024 202 240 303 226
E94ASxE2454 245 302 368 275
E94ASxE2924 292 361 438 330
E94ASxE3664 366 443 549 415
E94ASxE4604 460 550 690 522
E94ASxE5724 572 610 858 550
E94ASxE6354 635 678 953 610
E94ASxE6954 695 730 1043 653
I
aN2
Rated value of continuous output current at a frequency of 0Hz
(standard operation)
I
aNhc
Increased continuous output current at a frequency of 0Hz
I
aMhc
Maximum output current (overload current)
z Periodic load change of 10 s with I
aMhc
and recovery time of 50 s with I
aMre
I
aMre
Maximum output current during the recovery time of 50 s
Sinusoidal filter assignments changed for this operating mode:
Motor cable lengths when sinusoidal filters and line filters are used
Compliance with the EMC protection requirement C2
Type
Setting C01199 Sinusoidal filter shielded
unshielded
Switching
frequency
E94ASxE2924 ”Mode 1” EZS3-480A200 150 m
-m
2kHz
or
4kHz