Manual
Single-axis controllers
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
4
58
EDS94SPP101 EN 7.1
For the selection ”Mode 2“:
Output currents [A] at switching frequency
2kHz
Type I
aN2
I
aNhc
I
aMhc
I
aMre
E94ASxE1454 145 177 195 168
E94ASxE1724 172 212 233 201
E94ASxE2024 202 260 286 247
E94ASxE2454 245 315 347 299
E94ASxE2924 292 395 434 375
E94ASxE3664 366 480 528 456
E94ASxE4604 460 600 660 570
E94ASxE5724 572 658 724 625
E94ASxE6354 635 745 820 708
E94ASxE6954 695 800 880 760
I
aN2
Rated value of continuous output current at a frequency of ≥ 0Hz
(standard operation)
I
aNhc
Increased continuous output current at a frequency of ≥ 0Hz
I
aMhc
Maximum output current (overload current)
z Periodic load change of 60 s with I
aMhc
and recovery time of 120 s with I
aMre
I
aMre
Maximum output current during the recovery time
Sinusoidal filter assignments changed for this operating mode:
Motor cable lengths when sinusoidal filters and line filters are used
Compliance with the EMC protection requirement C2
Type
Setting C01199 Sinusoidal filter shielded
unshielded
Switching
frequency
E94ASxE2024
”Mode 2”
EZS3-350A200
150 m
-m
2kHz
or
4kHz
E94ASxE2924 EZS3-480A200
E94ASxE4604 EZS3-480A200
(2 in parallel)