Manual

Single-axis controllers
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 400 V
4
59
EDS94SPP101 EN 7.1
Rated data for internal brake chopper
R
Bmin
[Ω]
I
BRmax
[A]
P
BRmax
[kW]
I
BRd
[A]
P
Bd
[kW]
t
Z
[s]
t
on
[s]
t
fp
[s]
Type
E94ASxE0024 82
8.8 6.4 3.9 1.3 5 0.7 1.1
E94ASxE0034 82 8.8 6.4 3.9 1.3 5 0.7 1.1
E94ASxE0044 47 15.4 11.2 6.3 1.9 5 0.6 1.0
E94ASxE0074 47 15.4 11.2 7.4 2.6 5 0.8 1.0
E94ASxE0134 27 26.9 19.5 13.2 4.7 5 0.8 1.2
E94ASxE0174 18 40.3 29.2 18.9 6.4 5 0.7 1.1
E94ASxE0244 18 40.3 29.2 22.8 9.3 5 1.1 1.6
E94ASxE0324 18 40.3 29.2 26.5 12.6 600 260 600
E94ASxE0474 15 48.3 35.0 35.2 18.6 600 320 600
E94ASxE0594 15 48.3 35.0 41.0 25.3 600 430 600
E94ASxE0864 7.5 96.7 70.1 71.1 37.9 600 320 600
E94ASxE1044 7.5 96.7 70.1 78.7 46.3 600 400 600
E94ASxE1454 5.0 145 105 79 31.5 600 60 62
E94ASxE1724 4.3 169 122 93 36.7 600 60 62
E94ASxE2024 3.5 207 150 113 45.1 600 60 62
E94ASxE2454 2.8 259 188 142 56.3 600 60 62
E94ASxE2924 2.3 315 229 173 68.6 600 60 62
E94ASxE3664 1.8 414 300 227 90.1 600 60 62
E94ASxE4604 1.4 518 375 266 99 300 30 33
E94ASxE5724 1.2 604 438 287 99 300 28 32
E94ASxE6354 1.1 659 478 300 99 300 25 29
E94ASxE6954 1.1 659 478 300 99 300 25 29
R
Bmin
Minimum brake resistance, nominal value ±10 %
I
BRmax
Peak current
P
BRmax
Peak braking power
I
BRd
Continuous current RMS - important for the dimensioning of the cables
P
Bd
Continuous braking power
t
Z
Cycle time, periodic load change with running time and recovery time
t
on
Running time
t
Z
-t
on
Recovery time
t
fp
Maximum running time without initial load and compliance with the recovery
time
Note on the brake chopper data
The brake chopper can output the peak braking power maximally for the specified time t
on
within a cycle time t
Z
.
The brake chopper can output the peak braking power from unloaded s tates once for the
time t
fp
, e. g. after mains connection or after a recovery time of > 5 x t
Z
.
If the times are exceeded, the brake chopper is clocked so that only the continuous braking
power is output. This serves to the protection of the brake chopper, however, it does not
protect the brake resistor. The brake resistor connected can be protected separately by
parameterisation (C00129 ... C00133) or a thermal contact.
Further information can be found in the software manual.