Manual
Single-axis controllers
Rated data (devices for 400/500V mains)
Operation at rated mains voltage 500 V
4
65
EDS94SPP101 EN 7.1
Rated data for internal brake chopper
R
Bmin
[Ω]
I
BRmax
[A]
P
BRmax
[kW]
I
BRd
[A]
P
Bd
[kW]
t
Z
[s]
t
on
[s]
t
fp
[s]
Type
E94ASxE0024 82
9.6 7.6 4.3 1.5 5 0.7 1.1
E94ASxE0034 82 9.6 7.6 4.3 1.5 5 0.7 1.1
E94ASxE0044 47 16.8 13.3 6.9 2.3 5 0.6 1.0
E94ASxE0074 47 16.8 13.3 8.1 3.1 5 0.8 1.0
E94ASxE0134 27 29.3 23.1 14.4 5.5 5 0.8 1.2
E94ASxE0174 18 43.9 34.7 20.6 7.6 5 0.7 1.1
E94ASxE0244 18 43.9 34.7 24.8 11.1 5 1.1 1.6
E94ASxE0324 18.0 43.9 34.7 28.9 15.0 600 260 600
E94ASxE0474 15.0 52.7 41.6 38.4 22.0 600 320 600
E94ASxE0594 15.0 52.7 41.6 44.8 30.0 600 430 600
E94ASxE0864 7.5 105.3 83.2 77.5 45.0 600 320 600
E94ASxE1044 7.5 105.3 83.2 85.7 55.0 600 400 600
E94ASxE1454 5.0 158 125 87 37.4 600 60 62
E94ASxE1724 4.3 184 145 101 43.5 600 60 62
E94ASxE2024 3.5 226 178 124 53.5 600 60 62
E94ASxE2454 2.8 282 223 154 66.9 600 60 62
E94ASxE2924 2.3 343 271 188 81.4 600 60 62
E94ASxE3664 1.8 451 357 247 107 600 60 62
E94ASxE4604 1.4 564 446 289 117 300 30 33
E94ASxE5724 1.2 658 520 312 117 300 28 32
E94ASxE6354 1.1 718 567 327 117 300 25 29
E94ASxE6954 1.1 718 567 327 117 300 25 29
R
Bmin
Minimum brake resistance, nominal value ±10 %
I
BRmax
Peak current
P
BRmax
Peak braking power
I
BRd
Continuous current RMS - important for the dimensioning of the cables
P
Bd
Continuous braking power
t
Z
Cycle time, periodic load change with running time and recovery time
t
on
Running time
t
Z
-t
on
Recovery time
t
fp
Maximum running time without initial load and compliance with the recovery
time
Note on the brake chopper data
The brake chopper can output the peak braking power maximally for the specified time t
on
within a cycle time t
Z
.
The brake chopper can output the peak braking power from unloaded s tates once for the
time t
fp
, e. g. after mains connection or after a recovery time of > 5 x t
Z
.
If the times are exceeded, the brake chopper is clocked so that only the continuous braking
power is output. This serves to the protection of the brake chopper, however, it does not
protect the brake resistor. The brake resistor connected can be protected separately by
parameterisation (C00129 ... C00133) or a thermal contact.
Further information can be found in the software manual.