Manual
Single-axis controllers
Rated data (devices for 400/500V mains)
Fuses and cable cross-sections
4
66
EDS94SPP101 EN 7.1
4.3.5 Fuses and cable cross-sections
Basis of the data
Mains Voltage Voltage range Frequency range
U
LN
[V] U
LN
[V] f[Hz]
3/PE AC 230 ... 500 180-0%...550+0% 45 ... 65
Operation with external mains choke/mains filter
Type
Installation according to EN 60204-1
1)
Installation according
to UL
2)
FI
3)
c d L1, L2, L3 - Laying system e L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E94ASxE0024 C10 - 1,5 1,5 - 10 16 ≥ 300
E94ASxE0034 C10 - 1.5 1.5 - 10 16 ≥ 300
E94ASxE0044 C10 - 1.5 1.5 - 10 16 ≥ 300
E94ASxE0074 C16 - 2.5 2.5 - 15 14 ≥ 300
E94ASxE0134 C20 - 2.5 2.5 - 20 12 ≥ 300
E94ASxE0174 C25 - 4 4 - 25 10 ≥ 300
E94ASxE0244 C32 - 10 6 - 40 8 ≥ 300
1)
The details are recommendations. Other designs/laying systems are possible (e.g. according to VDE 0298-4). The
cable cross-sections apply under the following conditions: the use of PVC-insulated copper cables, conductor
temperature < 70°C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
UL approved cables only, fuses and fuse holders must be used.
UL fuse: voltage 500 ... 600 V
3)
Universal-current sensitive earth-leakage circuit breaker
If several devices or cable lengths > 50 m are used, the circuit breaker may respond, depending on the cable type and
switching frequency.
c Circuit breaker
d Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
e Fuse
Observe national and regional regulations