Manual
Single-axis controllers
Rated data (devices for 400/500V mains)
Overcurrent operation
4
74
EDS94SPP101 EN 7.1
500 V
Type
I [A] in a cycle of 3 minutes d
f=2kHz f=4kHz f=8kHz f = 16 kHz
E94ASxE0024 2.8 1.4 2.8 1.4 2.0 1.0 - -
E94ASxE0034 4.7 2.4 4.7 2.4 3.3 1.6 - -
E94ASxE0044 7.5 3.8 7.5 3.8 5.3 2.6 - -
E94ASxE0074 13.2 6.6 13.2 6.6 9.2 4.6 - -
E94ASxE0134 24.4 12.2 24.4 12.2 17.1 8.5 - -
E94ASxE0174 31.0 15.5 31.0 15.5 21.7 10.8 - -
E94ASxE0244 44.2 22.1 44.2 22.1 30.8 15.4 - -
E94ASxE0324 57.6 28.8 57.6 28.8 42.0 21.0 - -
E94ASxE0474 70.5 35.3 70.5 35.3 53.9 26.7 - -
E94ASxE0594 88.5 44.3 88.5 44.3 53.7 26.8 - -
E94ASxE0864 129 64.5 129 64.5 96 48.2 - -
E94ASxE1044 156 78.0 156 78.0 103 51.0 - -
E94ASxE1454 218 109 218 109 164 81.2 - -
E94ASxE1724 258 129 258 129 194 96.3 - -
E94ASxE2024 303 152 303 152 228 113 - -
E94ASxE2454 368 184 314 157 240 120 - -
E94ASxE2924 438 219 374 187 286 143 - -
E94ASxE3664 549 275 468 234 359 179 - -
E94ASxE4604 690 345 552 276 391 193 - -
E94ASxE5724 858 429 686 343 429 217 - -
E94ASxE6354 953 476 762 381 476 241 - -
E94ASxE6954 1043 521 834 417 521 264 - -